6-26
F60 Feeder Protection System
GE Multilin
6.4 RECORDS
6 ACTUAL VALUES
6
6.4.5 BREAKER MAINTENANCE
PATH: ACTUAL VALUES
ÖØ
RECORDS
ÖØ
MAINTENANCE
Ö
BREAKER 1(2)
There is an identical menu for each of the breakers. The
BKR 1 ARCING AMP
values are in units of kA
2
-cycles. Refer to the
COMMANDS
ÖØ
CLEAR RECORDS
menu for clearing breaker arcing current records. The
BREAKER OPERATING TIME
is
defined as the slowest operating time of breaker poles that were initiated to open.
6.4.6 HI-Z RECORDS
PATH: ACTUAL VALUES
ÖØ
RECORDS
ÖØ
HIZ RECORDS
Two types of high impedance fault detection element records are stored in non-volatile memory and available from this
menu. If the element is triggered by a high impedance overcurrent condition, then the records are displayed in the
RMS 1
to
RMS 4
actual values. If the element is triggered by high impedance fault detection arcing algorithm, then the records are dis-
played in the
HIZ 1
to
HIZ 4
actual values. Refer to
High impedance fault detection
section in chapter 5 for more information.
BREAKER 1
BKR 1 ARCING AMP
φ
A:
0.00 kA2-cyc
MESSAGE
BKR 1 ARCING AMP
φ
B:
0.00 kA2-cyc
MESSAGE
BKR 1 ARCING AMP
φ
C:
0.00 kA2-cyc
MESSAGE
BKR 1 OPERATING TIME
φ
A: 0
ms
MESSAGE
BKR 1 OPERATING TIME
φ
B: 0
ms
MESSAGE
BKR 1 OPERATING TIME
φ
C: 0
ms
MESSAGE
BKR 1 OPERATING
TIME:
0 ms
HIZ RECORDS
FORCE TRIGGER:
No
MESSAGE
HIZ 1:NONE
1970/01/01 00:00:00
MESSAGE
HIZ 2:NONE
1970/01/01 00:00:00
MESSAGE
HIZ 3:NONE
1970/01/01 00:00:00
MESSAGE
HIZ 4:NONE
1970/01/01 00:00:00
MESSAGE
RMS 1:NONE
1970/01/01 00:00:00
MESSAGE
RMS 2:NONE
1970/01/01 00:00:00
MESSAGE
RMS 3:NONE
1970/01/01 00:00:00
MESSAGE
RMS 4:NONE
1970/01/01 00:00:00
Summary of Contents for F60 UR Series
Page 2: ......
Page 4: ......
Page 30: ...1 20 F60 Feeder Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 48: ...2 18 F60 Feeder Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 126: ...4 30 F60 Feeder Protection System GE Multilin 4 2 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 354: ...5 228 F60 Feeder Protection System GE Multilin 5 9 TESTING 5 SETTINGS 5 ...
Page 382: ...6 28 F60 Feeder Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 398: ...8 8 F60 Feeder Protection System GE Multilin 8 2 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Page 414: ...A 14 F60 Feeder Protection System GE Multilin A 1 PARAMETER LIST APPENDIXA A ...
Page 492: ...B 78 F60 Feeder Protection System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Page 530: ...D 10 F60 Feeder Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Page 542: ...E 12 F60 Feeder Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Page 558: ...x F60 Feeder Protection System GE Multilin INDEX ...