B-34
F60 Feeder Protection System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
72AC
Neg Seq Directional Overcurrent 1 Pos Seq Restraint
0 to 0.5
---
0.001
F001
63
72AD
Reserved (3 items)
0 to 1
---
1
F001
0
72B0
...Repeated for Neg Seq Directional Overcurrent 2
Breaker Arcing Current Settings (Read/Write Setting) (2 modules)
72C0
Breaker 1 Arcing Current Function
0 to 1
---
1
F102
0 (Disabled)
72C1
Breaker 1 Arcing Current Source
0 to 5
---
1
F167
0 (SRC 1)
72C2
Breaker 1 Arcing Current Initiate A
0 to 65535
---
1
F300
0
72C3
Breaker 1 Arcing Current Initiate B
0 to 65535
---
1
F300
0
72C4
Breaker 1 Arcing Current Initiate C
0 to 65535
---
1
F300
0
72C5
Breaker 1 Arcing Current Delay
0 to 65.535
s
0.001
F001
0
72C6
Breaker 1 Arcing Current Limit
0 to 50000
kA
2
-cyc
1
F001
1000
72C7
Breaker 1 Arcing Current Block
0 to 65535
---
1
F300
0
72C8
Breaker 1 Arcing Current Target
0 to 2
---
1
F109
0 (Self-reset)
72C9
Breaker 1 Arcing Current Events
0 to 1
---
1
F102
0 (Disabled)
72CA
...Repeated for Breaker 2 Arcing Current
dcmA Inputs (Read/Write Setting) (24 modules)
7300
dcmA Inputs 1 Function
0 to 1
---
1
F102
0 (Disabled)
7301
dcmA Inputs 1 ID
---
---
---
F205
“DCMA I 1"
7307
Reserved 1 (4 items)
0 to 65535
---
1
F001
0
730B
dcmA Inputs 1 Units
---
---
---
F206
“mA”
730E
dcmA Inputs 1 Range
0 to 6
---
1
F173
6 (4 to 20 mA)
730F
dcmA Inputs 1 Minimum Value
-9999.999 to 9999.999
---
0.001
F004
4000
7311
dcmA Inputs 1 Maximum Value
-9999.999 to 9999.999
---
0.001
F004
20000
7313
Reserved (5 items)
0 to 65535
---
1
F001
0
7318
...Repeated for dcmA Inputs 2
7330
...Repeated for dcmA Inputs 3
7348
...Repeated for dcmA Inputs 4
7360
...Repeated for dcmA Inputs 5
7378
...Repeated for dcmA Inputs 6
7390
...Repeated for dcmA Inputs 7
73A8
...Repeated for dcmA Inputs 8
73C0
...Repeated for dcmA Inputs 9
73D8
...Repeated for dcmA Inputs 10
73F0
...Repeated for dcmA Inputs 11
7408
...Repeated for dcmA Inputs 12
7420
...Repeated for dcmA Inputs 13
7438
...Repeated for dcmA Inputs 14
7450
...Repeated for dcmA Inputs 15
7468
...Repeated for dcmA Inputs 16
7480
...Repeated for dcmA Inputs 17
7498
...Repeated for dcmA Inputs 18
74B0
...Repeated for dcmA Inputs 19
74C8
...Repeated for dcmA Inputs 20
74E0
...Repeated for dcmA Inputs 21
74F8
...Repeated for dcmA Inputs 22
7510
...Repeated for dcmA Inputs 23
7528
...Repeated for dcmA Inputs 24
Disconnect switches (read/write settings)
7540
Disconnect switch 1 function
0 to 1
---
1
F102
0 (Disabled)
7541
Disconnect switch 1 name
---
---
---
F206
“SW 1"
7544
Disconnect switch 1 mode
0 to 1
---
1
F157
0 (3-Pole)
7545
Disconnect switch 1 open
0 to 65535
---
1
F300
0
7546
Disconnect switch 1 block open
0 to 65535
---
1
F300
0
7547
Disconnect switch 1 close
0 to 65535
---
1
F300
0
Table B–9: MODBUS MEMORY MAP (Sheet 26 of 53)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for F60 UR Series
Page 2: ......
Page 4: ......
Page 30: ...1 20 F60 Feeder Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 48: ...2 18 F60 Feeder Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 126: ...4 30 F60 Feeder Protection System GE Multilin 4 2 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 354: ...5 228 F60 Feeder Protection System GE Multilin 5 9 TESTING 5 SETTINGS 5 ...
Page 382: ...6 28 F60 Feeder Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 398: ...8 8 F60 Feeder Protection System GE Multilin 8 2 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Page 414: ...A 14 F60 Feeder Protection System GE Multilin A 1 PARAMETER LIST APPENDIXA A ...
Page 492: ...B 78 F60 Feeder Protection System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Page 530: ...D 10 F60 Feeder Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Page 542: ...E 12 F60 Feeder Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Page 558: ...x F60 Feeder Protection System GE Multilin INDEX ...