B-42
F60 Feeder Protection System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
9508
...Repeated for Direct Input/Output 23
9514
...Repeated for Direct Input/Output 24
9520
...Repeated for Direct Input/Output 25
952C
...Repeated for Direct Input/Output 26
9538
...Repeated for Direct Input/Output 27
9544
...Repeated for Direct Input/Output 28
9550
...Repeated for Direct Input/Output 29
955C
...Repeated for Direct Input/Output 30
9568
...Repeated for Direct Input/Output 31
9574
...Repeated for Direct Input/Output 32
FlexElement Actuals (Read Only) (16 modules)
9A01
FlexElement™ 1 Actual
-2147483.647 to 2147483.647
---
0.001
F004
0
9A03
FlexElement™ 2 Actual
-2147483.647 to 2147483.647
---
0.001
F004
0
9A05
FlexElement™ 3 Actual
-2147483.647 to 2147483.647
---
0.001
F004
0
9A07
FlexElement™ 4 Actual
-2147483.647 to 2147483.647
---
0.001
F004
0
9A09
FlexElement™ 5 Actual
-2147483.647 to 2147483.647
---
0.001
F004
0
9A0B
FlexElement™ 6 Actual
-2147483.647 to 2147483.647
---
0.001
F004
0
9A0D
FlexElement™ 7 Actual
-2147483.647 to 2147483.647
---
0.001
F004
0
9A0F
FlexElement™ 8 Actual
-2147483.647 to 2147483.647
---
0.001
F004
0
Teleprotection Inputs/Outputs (Read/Write Settings)
9B00
Teleprotection Function
0 to 1
---
1
F102
0 (Disabled)
9B01
Teleprotection Number of Terminals
2 to 3
---
1
F001
2
9B02
Teleprotection Number of Channels
1 to 2
---
1
F001
1
9B03
Teleprotection Local Relay ID
0 to 255
---
1
F001
0
9B04
Teleprotection Terminal 1 ID
0 to 255
---
1
F001
0
9B05
Teleprotection Terminal 2 ID
0 to 255
---
1
F001
0
9B06
Reserved (10 items)
0 to 1
---
---
F001
0
9B10
Teleprotection Input 1-n Default States (16 items)
0 to 3
---
1
F086
0 (Off)
9B30
Teleprotection Input 2-n Default States (16 items)
0 to 3
---
1
F086
0 (Off)
9B50
Teleprotection Output 1-n Operand (16 items)
0 to 65535
---
1
F300
0
9B70
Teleprotection Output 2-n Operand (16 items)
0 to 65535
---
1
F300
0
Teleprotection Inputs/Outputs Commands (Read/Write Command)
9B90
Teleprotection Clear Lost Packets
0 to 1
---
1
F126
0 (No)
Teleprotection Channel Tests (Read Only)
9B91
Teleprotection Channel 1 Status
0 to 2
---
1
F134
1 (OK)
9B92
Teleprotection Channel 1 Number of Lost Packets
0 to 65535
---
1
F001
0
9B93
Teleprotection Channel 2 Status
0 to 2
---
1
F134
1 (OK)
9B94
Teleprotection Channel 2 Number of Lost Packets
0 to 65535
---
1
F001
0
9B95
Teleprotection Network Status
0 to 2
---
1
F134
2 (n/a)
9BA0
Teleprotection Channel 1 Input States
0 to 1
---
1
F500
0
9BA1
Teleprotection Channel 2 Input States
0 to 1
---
1
F500
0
9BB0
Teleprotection Input 1 States, 1 per register (16 items)
0 to 1
---
1
F108
0 (Off)
9BC0
Teleprotection Input 2 States, 1 per register (16 items)
0 to 1
---
1
F108
0 (Off)
Cold Load Pickup (Read/Write Setting) (2 modules)
A010
Cold Load Pickup 1 Function
0 to 1
---
1
F102
0 (Disabled)
A011
Cold Load Pickup 1 Initiate
0 to 65535
---
1
F300
0
A012
Cold Load Pickup 1 Block
0 to 65535
---
1
F300
0
A013
Outage Time Before Cold Load Pickup 1
0 to 1000
s
1
F001
1000
A014
On Load Time Before Reset 1
0 to 1000000
s
0.001
F003
100000
A016
Cold Load Pickup 1 Source
0 to 5
---
1
F167
0 (SRC 1)
A017
Cold Load Pickup 1 Reserved
0 to 65535
---
1
F001
0
A018
...Repeated for Cold Load Pickup 2
VT Fuse Failure (Read/Write Setting) (6 modules)
A040
VT Fuse Failure Function
0 to 1
---
1
F102
0 (Disabled)
Table B–9: MODBUS MEMORY MAP (Sheet 34 of 53)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for F60 UR Series
Page 2: ......
Page 4: ......
Page 30: ...1 20 F60 Feeder Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 48: ...2 18 F60 Feeder Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 126: ...4 30 F60 Feeder Protection System GE Multilin 4 2 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 354: ...5 228 F60 Feeder Protection System GE Multilin 5 9 TESTING 5 SETTINGS 5 ...
Page 382: ...6 28 F60 Feeder Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 398: ...8 8 F60 Feeder Protection System GE Multilin 8 2 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Page 414: ...A 14 F60 Feeder Protection System GE Multilin A 1 PARAMETER LIST APPENDIXA A ...
Page 492: ...B 78 F60 Feeder Protection System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Page 530: ...D 10 F60 Feeder Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Page 542: ...E 12 F60 Feeder Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Page 558: ...x F60 Feeder Protection System GE Multilin INDEX ...