B.4 MEMORY MAPPING
B
B2CE
...Repeated for Report 3
B2F5
...Repeated for Report 4
B31C
...Repeated for Report 5
B343
...Repeated for Report 6
B36A
...Repeated for Report 7
B391
...Repeated for Report 8
B3B8
...Repeated for Report 9
B3DF
...Repeated for Report 10
B406
...Repeated for Report 11
B42D
...Repeated for Report 12
B454
...Repeated for Report 13
B47B
...Repeated for Report 14
B4A2
...Repeated for Report 15
B4C9
...Repeated for Report 16
IEC 61850 GGIO1 Configuration Settings (Read/Write Setting)
B500
Number of Status Indications in GGIO1
8 to 128
---
8
F001
8
B501
IEC 61850 GGIO1 Indication operands (128 items)
---
---
1
F300
0
IEC 61850 Configurable GOOSE Transmission (Read/Write Setting) (8 modules)
B5A0
IEC 61850 Configurable GOOSE Function
0 to 1
---
1
F102
0 (None)
B5A1
IEC 61850 Configurable GOOSE ID
---
---
---
F209
“GOOSEOut_x_”
B5C2
Configurable GOOSE Destination MAC Address
---
---
---
F072
0
B5C5
IEC 61850 Configurable GOOSE VLAN Transmit Priority
0 to 7
---
1
F001
4
B5C6
IEC 61850 Configurable GOOSE VLAN ID
0 to 4095
---
1
F001
0
B5C7
IEC 61850 Configurable GOOSE ETYPE APPID
0 to 16383
---
1
F001
0
B5C8
IEC 61850 Configurable GOOSE ConfRev
1 to 4294967295
---
1
F003
1
B5CA
Configurable GOOSE Dataset Items for Transmission
0 to 256
---
1
F232
0 (None)
B60A
...Repeated for Module 2
B674
...Repeated for Module 3
B6DE
...Repeated for Module 4
B748
...Repeated for Module 5
B7B2
...Repeated for Module 6
B81C
...Repeated for Module 7
B886
...Repeated for Module 8
IEC 61850 Configurable GOOSE Reception (Read/Write Setting) (8 modules)
B900
Configurable GOOSE Dataset Items for Transmission
0 to 128
---
1
F233
0 (None)
B940
...Repeated for Module 2
B980
...Repeated for Module 3
B9C0
...Repeated for Module 4
BA00
...Repeated for Module 5
BA40
...Repeated for Module 6
BA80
...Repeated for Module 7
BAC0
...Repeated for Module 8
Contact Inputs (Read/Write Setting) (96 modules)
BB00
Contact Input 1 Name
---
---
---
F205
“Cont Ip 1“
BB06
Contact Input 1 Events
0 to 1
---
1
F102
0 (Disabled)
BB07
Contact Input 1 Debounce Time
0 to 16
ms
0.5
F001
20
BB08
...Repeated for Contact Input 2
BB10
...Repeated for Contact Input 3
BB18
...Repeated for Contact Input 4
BB20
...Repeated for Contact Input 5
BB28
...Repeated for Contact Input 6
BB30
...Repeated for Contact Input 7
BB38
...Repeated for Contact Input 8
BB40
...Repeated for Contact Input 9
Table B–9: MODBUS MEMORY MAP (Sheet 41 of 53)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for F60 UR Series
Page 2: ......
Page 4: ......
Page 30: ...1 20 F60 Feeder Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 48: ...2 18 F60 Feeder Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 126: ...4 30 F60 Feeder Protection System GE Multilin 4 2 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 354: ...5 228 F60 Feeder Protection System GE Multilin 5 9 TESTING 5 SETTINGS 5 ...
Page 382: ...6 28 F60 Feeder Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 398: ...8 8 F60 Feeder Protection System GE Multilin 8 2 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Page 414: ...A 14 F60 Feeder Protection System GE Multilin A 1 PARAMETER LIST APPENDIXA A ...
Page 492: ...B 78 F60 Feeder Protection System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Page 530: ...D 10 F60 Feeder Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Page 542: ...E 12 F60 Feeder Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Page 558: ...x F60 Feeder Protection System GE Multilin INDEX ...