GE Multilin
F60 Feeder Protection System
C-3
APPENDIX C
C.2 SERVER DATA ORGANIZATION
C
C.2.6 MMXU: ANALOG MEASURED VALUES
A limited number of measured analog values are available through the MMXU logical nodes.
Each MMXU logical node provides data from a F60 current and voltage source. There is one MMXU available for each con-
figurable source (programmed in the
SETTINGS
ÖØ
SYSTEM SETUP
ÖØ
SIGNAL SOURCES
menu). MMXU1 provides data
from F60 source 1, and MMXU2 provides data from F60 source 2.
MMXU data is provided in two forms: instantaneous and deadband. The instantaneous values are updated every time a
read operation is performed by a client. The deadband values are calculated as described in IEC 61850 parts 7-1 and 7-3.
The selection of appropriate deadband settings for the F60 is described in chapter 5 of this manual.
IEC 61850 buffered and unbuffered reporting capability is available in all MMXU logical nodes. MMXUx logical nodes pro-
vide the following data for each source:
•
MMXU1.MX.TotW: three-phase real power
•
MMXU1.MX.TotVAr: three-phase reactive power
•
MMXU1.MX.TotVA: three-phase apparent power
•
MMXU1.MX.TotPF: three-phase power factor
•
MMXU1.MX.Hz: frequency
•
MMXU1.MX.PPV.phsAB: phase AB voltage magnitude and angle
•
MMXU1.MX.PPV.phsBC: phase BC voltage magnitude and angle
•
MMXU1.MX.PPV.phsCA: Phase CA voltage magnitude and angle
•
MMXU1.MX.PhV.phsA: phase AG voltage magnitude and angle
•
MMXU1.MX.PhV.phsB: phase BG voltage magnitude and angle
•
MMXU1.MX.PhV.phsC: phase CG voltage magnitude and angle
•
MMXU1.MX.A.phsA: phase A current magnitude and angle
•
MMXU1.MX.A.phsB: phase B current magnitude and angle
•
MMXU1.MX.A.phsC: phase C current magnitude and angle
•
MMXU1.MX.A.neut: ground current magnitude and angle
•
MMXU1.MX.W.phsA: phase A real power
•
MMXU1.MX.W.phsB: phase B real power
•
MMXU1.MX.W.phsC: phase C real power
•
MMXU1.MX.VAr.phsA: phase A reactive power
•
MMXU1.MX.VAr.phsB: phase B reactive power
•
MMXU1.MX.VAr.phsC: phase C reactive power
•
MMXU1.MX.VA.phsA: phase A apparent power
•
MMXU1.MX.VA.phsB: phase B apparent power
•
MMXU1.MX.VA.phsC: phase C apparent power
•
MMXU1.MX.PF.phsA: phase A power factor
•
MMXU1.MX.PF.phsB: phase B power factor
•
MMXU1.MX.PF.phsC: phase C power factor
C.2.7 PROTECTION AND OTHER LOGICAL NODES
The following list describes the protection elements for all UR-series relays. The F60 relay will contain a subset of protec-
tion elements from this list.
•
PDIF: bus differential, transformer instantaneous differential, transformer percent differential
Summary of Contents for F60 UR Series
Page 2: ......
Page 4: ......
Page 30: ...1 20 F60 Feeder Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 48: ...2 18 F60 Feeder Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 126: ...4 30 F60 Feeder Protection System GE Multilin 4 2 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 354: ...5 228 F60 Feeder Protection System GE Multilin 5 9 TESTING 5 SETTINGS 5 ...
Page 382: ...6 28 F60 Feeder Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 398: ...8 8 F60 Feeder Protection System GE Multilin 8 2 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Page 414: ...A 14 F60 Feeder Protection System GE Multilin A 1 PARAMETER LIST APPENDIXA A ...
Page 492: ...B 78 F60 Feeder Protection System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Page 530: ...D 10 F60 Feeder Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Page 542: ...E 12 F60 Feeder Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Page 558: ...x F60 Feeder Protection System GE Multilin INDEX ...