GE Multilin
750/760 Feeder Management Relay
5-51
5 SETPOINTS
5.6 S5 PROTECTION
5
Figure 5–17: GROUND DIRECTIONAL LOGIC
5.6.5 SENSITIVE GROUND CURRENT
a) MAIN MENU
PATH: SETPOINTS
ÖØ
S5 PROTECTION
ÖØ
SENSTV GND CURRENT
Two sensitive ground overcurrent elements and a restricted earth fault element are provided. One time overcurrent element
and one instantaneous element. Sensitive ground overcurrent elements can be controlled by the sensitive ground direc-
tional element allowing operation for faults in the permitted direction only. Also, the elements can be blocked individually or
as a group by logic inputs.
SENSTV GND CURRENT
[ENTER] for more
SENSTV GND TIME OC
[ENTER] for more
SENSTV GND INST OC
[ENTER] for more
SENSTV GND DIRECTN
[ENTER] for more
RESTRICTED EF
[ENTER] for more
ENTER
ESCAPE
ð
ð
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE