5-86
750/760 Feeder Management Relay
GE Multilin
5.7 S6 MONITORING
5 SETPOINTS
5
Figure 5–46: ANALOG INPUT RATE OF CHANGE MEASUREMENT
Note that connected analog input will still be read and displayed in
A2 METERING
ÖØ
A/I
if both
A/I RATE 1 FUNCTION
and
A/I
RATE 2 FUNCTION
are set to "Disabled".
Figure 5–47: ANALOG INPUT RATE OF CHANGE LOGIC
5.7.6 ANALOG OUTPUTS
PATH: SETPOINTS
ÖØ
S6 MONITORING
ÖØ
A/O
Ö
A/O 1(8)
There are three analog output channel types: A, B, and C (see Table 5–16: Analog Output Parameters on page 5–87 for
parameter-channel correspondence). Type A channel ranges extend from a minimum of 0 units. Type B channels range
between definite boundaries. Type C channels include the direction of flow. The following diagram illustrates these charac-
teristics.
A/O 1
[ENTER] for more
A/O 1 SOURCE:
Disabled
Range: See Table 5–16: Analog Output Parameters on
A/O 1 MIN:
–100.0 MW
Range: As per function selection. See Table 5–16:
Analog Output Parameters on page 5–87.
A/O 1 MAX:
100.0 MW
Range: As per function selection. See Table 5–16:
Analog Output Parameters on page 5–87.