5-126
750/760 Feeder Management Relay
GE Multilin
5.8 S7 CONTROL
5 SETPOINTS
5
f) RECLOSURE SHOTS 1 TO 4
PATH: SETPOINTS
ÖØ
S7 CONTROL
ÖØ
AR
ÖØ
RECLOSURE 1(4)
The above setpoints are programmed independently and are repeated for each of the Reclosure Shots 1 through 4. These
setpoints determine the dead time for a given shot and the overcurrent characteristics during that shot. Selections for shots,
that are greater than the maximum number of shots programmed in the scheme setup, will not be used by the scheme.
RECLOSURE 1
[ENTER] for more
DEADTIME BEFORE
RECLOSURE:
0.50 s
Range: 0.00 to 300.00 s in steps of 0.01
PHASE INST OC 1
BLOCKING: Disabled
Range: Enabled, Disabled
NEUTRAL INST OC 1
BLOCKING: Disabled
Range: Enabled, Disabled
GND INST OC
BLOCKING: Disabled
Range: Enabled, Disabled
SENSTV GND INST OC
BLOCKING: Disabled
Range: Enabled, Disabled
NEG SEQ INST OC
BLOCKING: Disabled
Range: Enabled, Disabled
PHASE TIME OC 1
RAISED PICKUP: 0%
Range: 0 to 100% in steps of 1
NEUTRAL TIME OC 1
RAISED PICKUP: 0%
Range: 0 to 100% in steps of 1
GND TIME OC
RAISED PICKUP: 0%
Range: 0 to 100% in steps of 1
SENSTV GND TIME OC
RAISED PICKUP: 0%
Range: 0 to 100% in steps of 1
NEG SEQ TIME OC
RAISED PICKUP: 0%
Range: 0 to 100% in steps of 1
SELECT SETPOINT
GROUP: Active
Range: Group 1, Group 2, Group 3, Group 4, Active