GE Multilin
750/760 Feeder Management Relay
7-45
7 COMMUNICATIONS
7.4 MODBUS MEMORY MAP
7
F49
ctd.
2000h
Operate (0=Not operating, 1=Operating)
4000h
Latched (0=Not latched, 1=Latched)
8000h
Latched Alarm (0=Not latched, 1=Latched)
0100h
Phase A (0=Phase A is not picked up/
operating, 1= Phase A is picked up/operating)
0200h
Phase B (0=Phase B is not picked up/
operating, 1= Phase B is picked up/operating)
0400h
Phase C (0=Phase C is not picked up/
operating, 1= Phase C is picked up/operating)
F50
POLARIZATION
0
Voltage
1
Current
2
Dual
F51
A100 SELF-TEST ERRORS
0001h
+32V Analog Out Volt Monitor (0 = OK, 1 = Fail)
0002h
+32V Switch In Volt Monitor (0 = OK, 1 = Failed)
0004h
Real Time Clock (0 = OK, 1 = Unable to Start)
0008h
Not Used
0010h
EEPROM Failure (0 = OK, 1 = Failed)
0020h
Internal Temperature (-40 to 70 °C)
(0 = OK, 1= Out of Range)
0040h
A/D Virtual Ground (0 = OK, 1 = Out of Spec)
0080h
Not Calibrated (0 = OK, 1 = Not Calibrated)
0100h
7
Not Used
8000h
Prototype Unit (0 = OK, 1 = Installed)
F52
2's COMPLEMENT SIGNED VALUE, 2 DECIMAL PLACES
DISTANCE TO FAULT
Example: -12.34 stored as -1234. Note: a value of 327.67
indicates that the distance could not be calculated.
F53
UNSIGNED VALUE, 2 DEC PLACES - LINE Z1 TO FAULT
Example: 12.34 stored as 1234. Note: a value of 655.35
indicates that the impedance could not be calculated
F54
FORCE LED STATE
0001h
LED #1 (Top) (0 = Off, 1 = On)
0002h
LED #2 (0 = Off, 1 = On)
0004h
LED #3 (0 = Off, 1 = On)
0008h
LED #4 (0 = Off, 1 = On)
0010h
LED #5 (0 = Off, 1 = On)
0020h
LED #6 (0 = Off, 1 = On)
0040h
LED #7 (0 = Off, 1 = On)
0080h
LED #8 (Bottom) (0 = Off, 1 = On)
F55
FRONT PANEL KEY
0
'0'
1
'1'
2
'2'
3
'3'
4
'4'
5
'5'
6
'6'
7
'7'
8
'8'
9
'9'
10
'.'
13
'Value Up'
14
'Value Down'
15
'Message Up'
Table 7–7: MEMORY MAP DATA FORMATS (SHEET 11 OF 17)
TYPE
VALUE
DESCRIPTION
1 2 3 4 5 6 7 8 9 For explanation of footnotes, see notes of end of Table.
F55
ctd.
16
'Message Down'
17
'Next'
18
'Enter'
19
'Escape'
20
'Setpoints'
21
'Actual'
22
'Reset'
23
'Open'
24
'Close'
25
'Help'
31
No Key
F56
TRANSFER FUNCTION
0
Disabled
1
Incomer 1
2
Incomer 2
3
Bus Tie
F57
OUTPUT RELAYS (3-7)
0004h
3 Alarm (0 = Do Not Operate, 1 = Operate)
0008h
4 Auxiliary (0 = Do Not Operate, 1 = Operate)
0010h
5 Auxiliary (0 = Do Not Operate, 1 = Operate)
0020h
6 Auxiliary (0 = Do Not Operate, 1 = Operate)
0040h
7 Auxiliary (0 = Do Not Operate, 1 = Operate)
F58
DEMAND MEASUREMENT TYPE
0
Thermal Exponential
1
Block Interval
2
Rolling Demand
F59
2
OVERCURRENT BLOCKING FLAGS
0001h
2
Phase Inst OC 1 (0 = Do Not Block, 1= Block)
0002h
2
Neutral Inst OC 1 (0 = Do Not Block, 1= Block)
0004h
2
Ground Inst OC (0 = Do Not Block, 1= Block)
0008h
2
Neg Seq Inst OC (0 = Do Not Block, 1= Block)
0010h
3
Sens Gnd Inst OC (0 = Do Not Block, 1= Block)
F61
C400 SELF TEST ERRORS
0001h
A100 Communications (0 = OK, 1 = Failing)
8000h
Prototype Unit (0 = OK, 1 = Installed)
F62
PORT USED FOR DNP
0
None
1
COM1
2
COM2
3
Front
F63
2
INPUTS 1-14 ASSERTED LOGIC
0
1
Disabled
1
1
Contact Close
2
1
Contact Open
3
1
Virtual On
4
1
Virtual Off
5
1
Closed
&
V
on
6
1
Closed
&
V
off
7
1
Open
&
V
on
8
1
Open
&
V
off
9
1
Closed
|
V
on
10
1
Closed
|
V
off
11
1
Open
|
V
on
Table 7–7: MEMORY MAP DATA FORMATS (SHEET 12 OF 17)
TYPE
VALUE
DESCRIPTION
1 2 3 4 5 6 7 8 9 For explanation of footnotes, see notes of end of Table.