8-6
750/760 Feeder Management Relay
GE Multilin
8.2 INPUTS/OUTPUTS
8 COMMISSIONING TESTS
8
9.2.
Set the monitored contact for the logic input programmed in setpoint message User Input A Source to the
closed state and the virtual input to the off state. Check that no diagnostic message is on the display with the
Auxiliary LED and relay deactivated.
9.3.
Set the monitored contact to the open state with the virtual input remaining in the off state. Check that no diag-
nostic message is on the display with the Auxiliary LED and relay deactivated.
9.4.
Leave the monitored contact in the open state and put the virtual input in the on state. Check that the diagnostic
message, either User Input A or the name programmed in setpoint User Input A Name, appears on the display
with the Auxiliary LED and relay activated. Check in the Event Recorder that the selected function has been
invoked.
9.5.
Set the monitored contact to the closed state and the virtual input to the off state. Check that the diagnostic
message is removed from the display with the Auxiliary LED and relay deactivated.
9.6.
Repeat steps 9.3 through 9.7 for all functions programmed to be asserted by a Open & Von input.
10. For
INPUT ASSERTED LOGIC
setpoints set to "Open & Voff":
10.1. Check that there is no logic input diagnostic message on the display.
10.2. Set the monitored contact for the logic input programmed in setpoint message User Input A Source to the
closed state and the virtual input to the on state. Check that no diagnostic message is on the display with the 3
auxiliary LED and relay deactivated.
10.3. Set the monitored contact to the open state with the virtual input remaining in the on state. Check that no diag-
nostic message is on the display with the Auxiliary LED and relay deactivated.
10.4. Leave the monitored contact in the open state and put the virtual input in the off state. Check that the diagnostic
message, either User Input A or the name programmed in setpoint User Input A Name, appears on the display
with the Auxiliary LED and relay activated. Check in the Event Recorder that the selected function has been
invoked.
10.5. Set the monitored contact to the closed state and the virtual input to the on state. Check that the diagnostic
message is removed from the display with the Auxiliary LED and relay deactivated.
10.6. Repeat steps 10.3 through 10.7 for all functions programmed to be asserted by a Open & Voff input.
11. For
INPUT ASSERTED LOGIC
setpoints set to "Closed | Von":
11.1. Check that there is no logic input diagnostic message on the display.
11.2. Set the monitored contact for the logic input programmed in setpoint message User Input A Source to the
closed state and the virtual input to the off state. Check that the diagnostic message, either User Input A or the
name programmed in setpoint User Input A Name, appears on the display with the Auxiliary LED and relay acti-
vated. Check in the Event Recorder that the selected function has been invoked.
11.3. Leave the monitored contact in the closed state and put the virtual input in the on state. Check that the diagnos-
tic message, the Auxiliary LED and relay remain activated.
11.4. Set the monitored contact to the open state and leave the virtual input in the on state. Check that the diagnostic
message, the Auxiliary LED and relay remain activated.
11.5. Leave the monitored contact in the open state and put the virtual input in the off state. Check that the diagnostic
message is removed from the display with the 3 Auxiliary LED and relay deactivated.
11.6. Repeat steps 11.3 through 11.7 for all functions programmed to be asserted by a Closed | Von input.
12. For
INPUT ASSERTED LOGIC
setpoints set to "Closed | Voff":
12.1. Check that there is no logic input diagnostic message on the display.
12.2. Set the monitored contact for the logic input programmed in setpoint message User Input A Source to the
closed state and the virtual input to the on state. Check that the diagnostic message, either User Input A or the
name programmed in setpoint User Input A Name, appears on the display with the Auxiliary LED and relay acti-
vated. Check in the Event Recorder that the selected function has been invoked.
12.3. Leave the monitored contact in the closed state and put the virtual input in the off state. Check that the diagnos-
tic message, the Auxiliary LED and relay remain activated.