c) FLASH MESSAGES
Flash messages are warning, error, or general information messages displayed in response to certain key presses. The
length of time these messages remain displayed can be programmed in
S1 RELAY SETUP
ÖØ
FRONT PANEL
Ö
FLASH MES-
SAGE TIME
. The factory default flash message time is 4 seconds.
Table 4–1: SELF-TEST WARNINGS
ERROR
SEVERITY
DESCRIPTION
A/D Virtual Ground
Major
This warning is caused by a failure of the analog to digital converter. The integrity of system
input measurements is affected by this failure.
Analog 32V
Minor
Caused by the loss of the +32 V DC power supply used to power analog outputs. Analog output
currents are affected by this failure.
Clock Not Set
Minor
Occurs if the clock has not been set.
Dry C32V
Minor
Caused by the loss of the +32 V DC power supply used to power dry contacts of logic inputs.
Logic inputs using internal power are affected by this failure.
EEPROM Corrupt
Major
Caused by detection of corrupted location(s) in the relay data memory which cannot be self-
corrected. Any function of the relay is susceptible to malfunction from this failure.
Factory Service
Major
This warning occurs when the relay is in factory service mode.
FLASH Corrupt
Major
This warning is caused by detection of a corrupted location in the program memory as
determined by a CRC error checking code. Any function of the relay is susceptible to
malfunction from this failure.
Force Analog Out
Minor
Occurs when the
FORCE A/O FUNCTION
setpoint is “Enabled”.
Force Relays
Minor
Occurs when the
FORCE OUTPUT RELAYS FUNCTION
setpoint is "Enabled".
Internal RS485
Minor
Caused by a failure of the internal RS485 communication link. Attempts to read actual values
or write setpoints will produce unpredictable results.
Internal Temp
Minor
Caused by the detection of unacceptably low (less than –40°C) or high (greater than +85°C)
temperatures detected inside the unit.
IRIG-B Failure
Minor
Caused when IRIG-B time synchronization has been enabled but the signal cannot be decoded.
Not Calibrated
Minor
This warning occurs when the relay has not been factory calibrated.
Pickup Test
Minor
Occurs when the
PICKUP TEST FUNCTION
setpoint is "Enabled".
Prototype Software
Minor
Occurs when prototype software has been loaded into the relay.
Relay Not Ready
Minor
This warning occurs when the
750/760 OPERATION
setpoint not been set to “Ready”.
RTC Crystal
Minor
This warning is caused by a failure of the Real Time Clock circuit. The ability of the relay to
maintain the current date and time is lost.
Simulation Mode
Minor
This warning occurs when the simulation feature of the relay is active.
ADJUSTED VALUE
HAS BEEN STORED
This flash message is displayed in response to the
key, while on a setpoint mes-
sage with a numerical value. The edited value had to be adjusted to the nearest multiple
of the step value before it was stored.
COMMAND IS BEING
EXECUTED
This flash message is displayed in response to executing a command message. Entering
"Yes" at a command will display the message
ARE YOU SURE?
. Entering "Yes" again will
perform the requested command and display this flash message.
DEFAULT MESSAGE
HAS BEEN ADDED
This flash message is displayed in response to pressing the
key, followed by the
key twice, on any message in
S1 RELAY SETUP
ÖØ
DEFAULT MESSAGES
.
DEFAULT MESSAGE
HAS BEEN REMOVED
This message is displayed in response to pressing the
key, followed by the
key
twice, on any selected default message in
S1 RELAY SETUP
ÖØ
DEFAULT MESSAGES
.
ENTER PASSCODE
IS INVALID
This flash message is displayed in response to an incorrectly entered passcode when
attempting to enable or disable setpoint access.
ENTRY MISMATCH -
CODE NOT STORED
This message is displayed while changing the password with the
S1 RELAY SETUP
Ö
PASSCODE
ÖØ
CHANGE PASSCODE
setpoint. If the passcode entered at the
PLEASE RE-
ENTER A NEW PASSCODE
prompt is different from the one entered
PLEASE ENTER A
NEW PASSCODE
prompt, the relay dumps the new passcode and display this message
ENTER
ENTER
ENTER