5-66
750/760 Feeder Management Relay
GE Multilin
5.6 S5 PROTECTION
5 SETPOINTS
5
d) OVERVOLTAGE
PATH: SETPOINTS
ÖØ
S5 PROTECTION
ÖØ
VOLTAGE
ÖØ
OVERVOLTAGE 1(2)
To protect voltage sensitive loads and circuits against sustained overvoltage conditions, the Overvoltage 1 and 2 protection
features can be used to either cause a trip or generate an alarm when the voltage exceeds a specified voltage value for a
specified time delay. The setpoints above are repeated for both Overvoltage 1 and Overvoltage 2.
Figure 5–30: OVERVOLTAGE LOGIC
OVERVOLTAGE 1
[ENTER] for more
OVERVOLTAGE 1
FUNCTION: Disabled
Range: Disabled, Trip, Alarm, Latched Alarm, Control
OVERVOLTAGE 1
RELAYS (3-7): -----
Range: Any combination of 3 to 7 Auxiliary relays
OVERVOLTAGE 1
PICKUP: 1.25 x VT
Range: 0.00 to 1.25 x VT in steps of 0.01
OVERVOLTAGE 1
DELAY:
2.0 s
Range: 0.0 to 6000.0 s in steps of 0.1
PHASES REQUIRED FOR
OPERATION: All Three
Range: Any One, Any Two, All Three