GE Multilin
750/760 Feeder Management Relay
5-89
5 SETPOINTS
5.7 S6 MONITORING
5
Figure 5–49: OVERFREQUENCY LOGIC
5.7.8 EQUIPMENT
a) MAIN MENU
PATH: SETPOINTS
ÖØ
S6 MONITORING
ÖØ
EQUIPMENT
The equipment monitoring features are provided to detect failures or unusual operating conditions of the feeder circuit
breaker and the bus VTs.
b) TRIP COUNTER
PATH: SETPOINTS
ÖØ
S6 MONITORING
ÖØ
EQUIPMENT
Ö
TRIP COUNTER
When the total number of trips detected reaches the
TRIP COUNTER LIMIT
setpoint, an output will occur.
EQUIPMENT
[ENTER] for more
TRIP COUNTER
[ENTER] for more
ARCING CURRENT
[ENTER] for more
BRKR OPERATION
[ENTER] for more
COIL MON 1
[ENTER] for more
COIL MON 2
[ENTER] for more
VT FAILURE
[ENTER] for more
TRIP COUNTER
[ENTER] for more
TRIP COUNTER
FUNCTION: Disabled
Range: Disabled, Alarm, Latched Alarm, Control
TRIP COUNTER
RELAYS (3-7): -----
Range: Any combination of 3 to 7 Auxiliary relays
TRIP COUNTER
LIMIT: 10000 Trips
Range: 1 to 10000 Trips in steps of 1
ENTER
ESCAPE
ð
ð
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
ENTER
ESCAPE
ð
ð
MESSAGE
ESCAPE
MESSAGE
ESCAPE