6-6
750/760 Feeder Management Relay
GE Multilin
6.2 A1 STATUS
6 ACTUAL VALUES
6
6.2.3 LAST TRIP DATA
PATH: ACTUAL VALUES
Ö
A1 STATUS
ÖØ
LAST TRIP DATA
Independent of the event recorder, the relay captures the system information at the time of the last trip event. This informa-
tion includes a time and date stamp, trip cause, phase current, ground current, sensitive ground current, neutral current,
voltages, system frequency, and the analog input. If more than one protection element trips for a fault (for example, both the
Phase and Neutral Instantaneous Overcurrent 1 elements) then only the first trip event detected by the relay will have Last
Trip Data captured. This information cannot be cleared; data for a new trip overwrites the previous trip data.
LAST TRIP DATA
[ENTER] for more
DATE OF LAST TRIP:
Mar 16 1997
Range: Date in format shown
TIME OF LAST TRIP:
12:34:56.789
Range: Time in format shown
TRIP: <
Φ
>
<Cause>
Range: See Section 6.5: A4 Event Recorder on page 6–
16 for range details.
A:
0
B:
0
C:
0
Amps
Range: 0 to 65535 A
GND CURRENT:
0 A
Range: 0 to 65535 A
SENSTV GND CURRENT:
0 A
Range: 0 to 655.35 A
NEUTRAL CURRENT:
0 A
Range: 0 to 65535 A
AN:
0.00
BN:
0.00
CN:
0.00
kVolts
Range: On, Off. Seen only if
S2 SYSTEM SETUP
ÖØ
BUS VT SENSING
ÖØ
VT CONNECTION TYPE
is
"
Wye
"
AB:
0.00
BC:
0.00
CA:
0.00
kVolts
Range: On, Off. Not seen if
S2 SYSTEM SETUP
ÖØ
BUS
VT SENSING
ÖØ
VT CONNECTION TYPE
is
"
Wye
"
NEUTRAL VOLTAGE:
0.00 kV
Range: 0 to 655.35 kV
SYSTEM FREQ:
0.00 Hz
Range: 0.00 to 90.00 Hz
A/I:
0
μ
A
Range: 0 to 655.35 units. Units programmed in
S6
MONITORING
ÖØ
A/I
Ö
A/I SETUP
ÖØ
A/I UNITS
ENTER
ESCAPE
ð
ð
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE