6-12
750/760 Feeder Management Relay
GE Multilin
6.3 A2 METERING
6 ACTUAL VALUES
6
The actual values messages for three-phase and Phase A power are shown above. Similar power messages follow for
Phases B and C.
The relay calculates and displays the real, reactive, and apparent power of the system. Both three phase and single phase
quantities are given. The relationship of these power quantities is illustrated in the power plane, as shown in the power
quantity relationships figure that follows. If the
VT CONNECTION TYPE
setpoint "None", all three phase quantities are dis-
played as zero and all single phase quantities disappear. All power quantities auto-range to show units appropriate to the
nominal power which is defined as:
(EQ 6.11)
6.3.7 ENERGY
PATH: ACTUAL VALUES
ÖØ
A2 METERING
ÖØ
ENERGY
The relay uses three phase power quantities to determine total energy consumption. All energy quantities can be reset to
zero with the
S1 RELAY SETUP
ÖØ
CLEAR DATA
ÖØ
CLEAR ENERGY USE DATA
setpoint command. Energy cost is also calcu-
lated based on the average billing rate programmed in the
S2 SYSTEM SETUP
ÖØ
PWR SYSTEM
ÖØ
COST OF ENERGY
set-
point. Although billing rate structures are usually more complex, these values provide approximate costs. Energy quantities
auto-range to show units appropriate to the nominal power.
Power quantities in the positive direction are added to the positive values; power quantities in the opposite direction are
added to the negative values.
The 750/760 is not a revenue class meter and cannot be used for billing purposes.
Table 6–1: POWER QUANTITIES
NOMINAL POWER (P
N
)
POWER UNITS
RESOLUTION
P
N
<
1 MVA
kW, kvar, kVA, kWhr, kvarhr
1
1 MVA
≤
P
N
<
10 MVA
MW, Mvar, MVA, MWhr, Mvarh
0.01
10 MVA
≤
P
N
MW, Mvar, MVA, MWhr, Mvarh
0.1
ENERGY
[ENTER] for more
POSITIVE WATTHOURS:
0.0 MWh
Range: 0 to 4 x 10
6
MWh. See Table 6–1: Power
Quantities for further explanation of units.
POSITIVE WATTHOUR
COST: $
0
Range: 0 to $4 x 10
9
NEGATIVE WATTHOURS:
0.0 MWh
Range: 0 to 4 x 10
6
MWh. See Table 6–1: Power
Quantities for further explanation of units.
NEGATIVE WATTHOUR
COST: $
0
Range: 0 to $4 x 10
9
POSITIVE VARHOURS:
0.0 Mvarh
Range: 0 to 4 x 10
6
Mvarh. See Table 6–1: Power
Quantities for further explanation of units.
NEGATIVE VARHOURS:
0.0 Mvarh
Range: 0 to 4 x 10
6
Mvarh. See Table 6–1: Power
Quantities for further explanation of units.
ENERGY USE DATA LAST