Critical Power
Modifications reserved
Page 45/91
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
User Manual
TLE Series 160 - 500 UL S2B
eBOOST SCREEN (option)
This screen is displayed only when
eBoost™ Operation Mode
is available
(option).
Enabled
This parameter (values
Yes
/
No)
enables
or disables the
eBoost™ Operation
Mode
.
If the value is
“Yes”
and the current time
is in the interval for the current day, the
eBoost™ Operation Mode
is active.
In case of RPA Parallel System
If
eBoost™ Operation Mode
is currently disabled
(No)
and
Q1
is closed, when
programming it to enable
(Yes)
the selected configuration will automatically be
propagated to all units in the
RPA Parallel System
.
The activation / deactivation of
eBoost™ Operation Mode
is indicated each time in the event list
.
In order to check the
Inverter
function, at least
1 minute
of
VFI
mode must be programmed during the
week (the
Yes/No
parameter is automatically disabled if this condition is not satisfied)
.
In case this minimum time in
VFI mode
is not respected, the
eBoost™ Operation Mode
will be disabled
.
If the value is
“No”
, the UPS is normally operating in
VFI / double conversion mode
at all times
.
When the UPS is in
eBoost™ Operating Mode
the
eBoost
LED
is ON (green
light).
NOTE !
The configuration of the activation schedule can only be updated when
eBoost™ Operation
Mode
is disabled (Enabled: No)
.
DAY
For the weekdays from
“Monday
to
Sunday”,
the edit mode (edit day) allows to define time intervals
when the UPS is operating in
eBoost™ Operation Mode
. The hour is given in 24-hour format.
These intervals are defined by:
Start Time
:
The hour of the day after which the
eBoost™ Operation Mode
is enabled.
The
eBoost™ Operation Mode
is enabled until the following
“Stop Time”
time is reached
(the
“Stop Time”
time of the same day if this is later than the
“Start Time”
time, the
“Stop
Time”
time of the following day otherwise).
Stop Time
:
The hour of the day before which the
eBoost™ Operation Mode
is enabled.
The
eBoost™ Operation Mode
is enabled starting from the preceding
“Start Time”
time (the
“Start Time”
time of the same day if this is earlier than the
“Stop Time”
time, the
“Start Time”
time of the previous
day otherwise).
Identical times for
“Start Time”
and
“Stop Time”
maintain the existing mode only in case the previous
command was
“Start Time”
and the following command will be
“Stop Time”
.