Critical Power
Modifications reserved
Page 3/7
GE_UPS_TDS_TLE_SUL_40K_M15_US_1US_V010.docx
Technical Data Sheet
TLE Scalable Series 40 - 150 UL S1
GENERAL DATA
Topology
VFI, double conversion
Nominal output apparent power
from PF=0.6 lag. to PF=0.9 lead.
KVA
40
50
80
100
120
150
Nominal output active power at PF=1
kW
40
50
80
100
120
150
Efficiency at 100% load PF=0.9 lag. / 1 in VFI
& PF=1 in Eco-Mode
% VFI
95.6 / 95.5 95.6 / 95.5 95.7 / 95.6 95.6 / 95.5 95.6 / 95.5 95.6 / 95.4
Eco-Mode
98.6
98.8
98.8
98.9
98.9
98.9
Efficiency at 75% load PF=0.9 lag. / 1 in VFI
& PF=1 in Eco-Mode
% VFI
95.7 / 95.6 95.7 / 95.6 95.8 / 95.7 95.8 / 95.7 95.8 / 95.7 95.9 / 95.7
Eco-Mode
98.3
98.4
98.5
98.6
98.7
98.7
Efficiency at 50% load PF=0.9 lag. / 1 in VFI
& PF=1 in Eco-Mode
% VFI
95.2 / 95.1 95.6 / 95.5 95.6 / 95.5 95.7 / 95.6 95.7 / 95.5 95.9 / 95.7
Eco-Mode
97.7
98.0
98.2
98.3
98.4
98.4
Audible noise level
dB(A)
62
Battery type
Valve regulated lead-acid (VRLA), vented lead-acid, NiCd
Operating temperature range
UPS:
32°F ÷ 104°F / 0°C ÷ 40°C (up to 122F / 50°C subjected to conditions)
Storage temperature range
UPS:
-13°F ÷ +131°F
Battery:
-4°F ÷ +104°F
(higher the temperature, shorter
the storage time of the battery)
-25°C ÷ +55°C
-20°C ÷ +40°C
Max. altitude without power derating
Power derating (according to EN/IEC 62040-
3)
1000m
1500m: -2.5% / 2000m: -5% / 2500m: -7.5% / 3000m: -10%
Protection degree
IP 30 (IEC 60529 - ANSI/NEMA 60529)
Standards
UL 1778 UL marking
EMC (Electromagnetic Compatibility)
EN/IEC 62040-2 Category C3 (Category C2 as option)
Electrostatic discharge immunity
4kV contact / 8kV air discharge
Internal protection
All internal live parts shrouded
Transport
On pallet- Cabinet suitable for handling by forklift
Color
RAL 9005 (black)
Installation
Minimum distance from the wall 2” / 5 cm and floor fixed
Service access
Front and top access only
External cable connections
Bottom at the front of the cabinet or top with lateral sidecar
Cooling
Enforced ventilation with fan failure detection
Paralleling (RPA version)
Up to 6 units for redundancy or capacity in RPA configuration (option)
Eco-Mode Operation
Standard
RECTIFIER
Rectifier bridge
Three phase, IGBT rectifier, overtemperature protection
Standard input voltage
Nominal: 3 x 480V + N
Rectifier accepted ph-ph voltage range: 410V ÷ 550V (wider voltages subject to de-rated loads)
Other input voltages
On request
Input frequency
60 Hz +/-10% (54 ÷ 66 Hz)
Power factor
0.99
Input current THD
<3%
Inrush current
Limited by soft-start circuit
Power walk-in
15 seconds (programmable)
Output voltage tolerance
+/- 1%
Battery voltage ripple
<1%
Battery current ripple
Max. 5% the battery capacity [Ah], expressed in A
Battery charging characteristic
IU (DIN 41773), T° compensated floating voltage
Battery charging current limit
Programmable
Input power data
kW
40
50
80
100
120
150
Input power at inverter nominal load and charged battery
at PF=0.9 lag.
kW 38.1 47.7 76.3 95.3 114.4 143.0
at PF=1.0 lag.
42.4 53.0 84.7 105.9 127.1 158.9
Max. input power at inverter nominal load and max. battery recharge current
kW 48.5 59.1 96.9 118.1 145.4 177.2
Standard battery charging current at the beginning of battery recharge at
nominal load (programmable)
A
12
12
24
24
36
36
UPS OUTPUT POWER CAPABILITY
Output UPS power versus power factor for:
Inductive loads
Resistive loads
Capacitive loads