1200-2000 Series Fire Panels, Repeaters, and Emulators
Interconnection and Wiring Guide
26
4 First-time start-up and configuration
This section describes first-time start-up, the DIP switch, software, and protocol configuration options
for your product.
4.1 First-time
start-up
When first starting up the control panel the FC12xx / FC20xx CPU module (located inside the control
panel door) must be configured as follows:
•
Memory switch
LOCKED
•
Service Mode switch
OFF
The memory should only be unlocked when prompted during the initial start-up procedure.
4.2
Configuration of 2000 series panels
Use the panel DIP switch located on the host power supply board to set the system protocol, mode,
and language.
4.2.1
Protocol selection
Use DIP switches 7 and 8 to select the protocol.
Table 3: Protocol selection (DIP switches 7 and 8)
1
2
3
4
5
6
7
8
Protocol
ON
OFF
900 series protocol
OFF
OFF
2000 series protocol
4.2.2 Mode
selection
Use DIP switches 4 to 6 to select the panel operating mode.
Table 4: Mode selection (DIP switches 4 to 6)
1
2
3
4
5
6
7
8
Mode
OFF
OFF
OFF
EN mode
OFF
OFF
ON
VdS mode (if VdS module installed)
OFF
ON
OFF
NEN mode
OFF
ON
ON
EP mode
ON
OFF
OFF
BS mode