1200-2000 Series Fire Panels, Repeaters, and Emulators
Interconnection and Wiring Guide
33
Current requirements
Table 6: Normal operation (battery powered)
FP12XX
FR1200/FR2000
FP1216EN / FP1264 /
FP12xxN
Current required by system
200 mA (max)
200 mA (max)
200 mA (max)
Loop current
- 2 loops
- 127 devices/loop @ 340 µA/device (DP951)
86 mA
0 mA
86 mA
Auxiliary current
0 mA
0 mA
0 mA
Total normal current
286 mA
200 mA
286 mA
Table 7: Alarm operation (battery powered)
FP12XX
FR1200/FR2000
FP1216EN / FP1264 /
FP12xxN
286 mA (max)
200 mA (max)
286 mA (max)
Extra loop current (20 x LED @ 4 mA)
80 mA
0 mA
80 mA
Sounders (sounder board: outputs 1-4)
200 mA
0 mA
200 mA
Total alarm current
566 mA
200 mA
566 mA
Table 8: Normal operation (mains powered)
FP2416/2464 & FP2432/24128
FP2864/28255 &
FP2864N/28255N
Mains load (maximum)
200 VA
200 VA
Total output current (27.6 V)
4 A
4 A
Battery capacity I
AUX
= 0 (72H standby)
36 AH
58 AH
Battery capacity (maximum)
68 AH
68 AH
Required battery charging current (maximum
battery capacity)
3.05 A
3.05 A
Current required by system (I
SYS
)*
0.5 A
0.8 A
Available auxiliary current
0.45 A
0.15 A
*I
SYS
calculated at 252 x 900 series ionisation detectors (FP2416/64) 1008 x 900 series ionisation detectors (FP2864/255)