111
Block Modes
Actions of the FVP110 During
RCas mode
Remote Cascade mode. In RCas mode, the function block per-
forms the specified calculations based on the setpoint that is
input from host computer or others via the remote cascade
parameter, and outputs the result.
Table 27 shows examples of block mode combinations in a
FVP110. When a block changes mode or the data status of a
signal changes for some reason, the other blocks connected to
that block identify the change by detecting the change in status
of an input signal, and change their modes, too. For example,
when the data status of BKCAL_IN in a PID block changes to
bad, the PID block automatically changes mode to IMan to ini-
tialize the control of its downstream block.
The respective modes that each block enters on occurrence of
a communication error and at a restart, and the handling of sig-
nals in each mode can be defined in the block’s option parame-
ters such as IO_OPTS and STATUS_OPTS. For details, see
the detailed descriptions of each function block.
Table 27
Examples of Block Mode Combinations and Operation Statuses
Operation Statuses
AI
PID
AO
TB
Transducer Initial setup, valve setup (when
carrying out auto tuning, travel calibration,
etc.)
-
-
O/S
O/S
Modification of parameter settings in
transducer block (modification of control
parameter settings, etc.)
-
-
O/S
O/S
Constant valve position control
-
-
Auto
Auto
PID single-loop control
Auto
Auto
Cas
Auto
PID cascade-loop control
Auto
Primary PID:
Auto
Secondary
PID: Cas
Cas
Auto
Summary of Contents for FVP110
Page 14: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 22: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 48: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 50: ...FVP 110 Fieldbus Valve Positioner Manual 34 GE Energy Block Diagram Figure 14 Block Diagram ...
Page 74: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 88: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 97: ...81 Dimensions Standard Specifications Dimensions Figure 46 Single Acting Actuator Dimensions ...
Page 99: ...83 Dimensions Standard Specifications Figure 48 Terminal Configuration ...
Page 100: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 115: ...99 View Object Configuration Table 11 View Object for Transducer Block continued ...
Page 117: ...101 View Object Configuration Table 18 View Object for AO Function Block ...
Page 119: ...103 View Object Configuration Table 20 View Object for OS Function Block ...
Page 121: ...105 View Object Configuration Table 22 View Object for Resource Block ...
Page 124: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 130: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 138: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 156: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 168: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 238: ...FVP 110 Fieldbus Valve Positioner Manual 222 GE Energy Table 72 LM Parameter Part List ...
Page 239: ...223 LM Parameter List Link Master Functions ...
Page 246: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 262: ...FVP 110 Fieldbus Valve Positioner Manual 246 GE Energy Table 85 Download Error Codes ...
Page 265: ...249 Comments on System Network Software Download Table 88 DOMAIN_DESCRIPTOR ...
Page 266: ...FVP 110 Fieldbus Valve Positioner Manual 250 GE Energy Table 89 DOMAIN_HEADER ...
Page 288: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 289: ...273 H Customer Maintenance Parts List ...
Page 290: ...FVP 110 Fieldbus Valve Positioner Manual 274 GE Energy ...
Page 291: ......