FVP 110 Fieldbus Valve Positioner Manual
126
GE Energy
Limit Switches
Limit switches monitor whether the valve position has reached a specified high or low limit
position and sends the high limit switch status to channel 2 and the low limit switch status
to channel 3. The thresholds (settings) for the high and low limit switches are set in
LIMSW_HI_LIM and LIMSW_LO_LIM. The switch statuses sent to channels 2 and 3
mean:
❑
0 = off (inactive)
❑
1 = on (active)
Hysteresis of 1% is applied for both High and Low limit switch. While the limit switch of
high side stays ON, it turns to OFF again only when the value of
FINAL_POSITION_VALUE becomes smaller by 1% or less than the value of
LIMSW_HI_LIM. Also, while limit switch of the low side stays ON, it turns to OFF again
only when the value of FINAL_POSITION_VALUE becomes greater by 1% or more than
the value of LIMSW_LO_LIM.
Auto Tuning
WARNING
This function strokes the valve over its full range. Do not
execute while valve is controlling the process. Keep away
from the movable parts to avoid injury.
Auto tuning checks the valve responses and automatically tunes control parameter
settings. The actions performed are chosen as shown in Table 34. To carry out auto
tuning, see “Carrying out Tuning” on page 61. Before carrying out auto tuning, change the
modes of the AO function block and transducer block to O/S.
Table 34
Types of Auto Tuning
Value
Comment
Description
1
Off
—
2
Travel calibration tuning at
stop point
Travel calibration at the tight-shut and full-open positions
3
Control parameter tuning
Tuning of control parameters
4
Travel calibration at stop point
and Control parameter tuning
Sequential execution of travel calibration and control parameter
tuning
5
Cancel execution
Cancellation of auto tuning execution
6
Travel calibration at stop point
without time out (for very large
valve)
Zero-point and span calibration at the tight-shut and full-open
positions without time out
Summary of Contents for FVP110
Page 14: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 22: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 48: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 50: ...FVP 110 Fieldbus Valve Positioner Manual 34 GE Energy Block Diagram Figure 14 Block Diagram ...
Page 74: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 88: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 97: ...81 Dimensions Standard Specifications Dimensions Figure 46 Single Acting Actuator Dimensions ...
Page 99: ...83 Dimensions Standard Specifications Figure 48 Terminal Configuration ...
Page 100: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 115: ...99 View Object Configuration Table 11 View Object for Transducer Block continued ...
Page 117: ...101 View Object Configuration Table 18 View Object for AO Function Block ...
Page 119: ...103 View Object Configuration Table 20 View Object for OS Function Block ...
Page 121: ...105 View Object Configuration Table 22 View Object for Resource Block ...
Page 124: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 130: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 138: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 156: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 168: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 238: ...FVP 110 Fieldbus Valve Positioner Manual 222 GE Energy Table 72 LM Parameter Part List ...
Page 239: ...223 LM Parameter List Link Master Functions ...
Page 246: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 262: ...FVP 110 Fieldbus Valve Positioner Manual 246 GE Energy Table 85 Download Error Codes ...
Page 265: ...249 Comments on System Network Software Download Table 88 DOMAIN_DESCRIPTOR ...
Page 266: ...FVP 110 Fieldbus Valve Positioner Manual 250 GE Energy Table 89 DOMAIN_HEADER ...
Page 288: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 289: ...273 H Customer Maintenance Parts List ...
Page 290: ...FVP 110 Fieldbus Valve Positioner Manual 274 GE Energy ...
Page 291: ......