FVP 110 Fieldbus Valve Positioner Manual
130
GE Energy
Table 36
XD_ERROR
Value
Comment
Description
100
Cycle count limit exceed
TOTAL_CYCLE_COUNT has reached CYCLE_COUNT_LIM.
101
Travel limit exceed
TOTAL_TRAVEL has reached TRAVEL_LIM.
102
Total open limit exceed
TOTAL_OPEN_TIME has reached OPEN_TIME_LIM.
103
Total close limit exceed
TOTAL_CLOSE_TIME has reached CLOSE_TIME_LIM.
104
Total near close limit exceed
TOTAL_NEAR_CLOSE_TIM has reached
NEAR_CLOSE_TIME_LIM.
110
Temperature out of range
The measured temperature is out of range.
111
Pressure sensor out of range
The measured pressure is out of range.
112
Position sensor out of range
The measured valve position is out of range.
113
Deviation warning
The deviation between the setpoint and measured valve
position has exceeded DEVIATION_LIM continuously for the
period specified by DEVIATION_TIME_TH [1].
114
Servo output drift warning
SERVO_OUTPUT_SIGNAL has reached
SERVO_WARN_LO_LIM or SERVO_WARN_HI_LIM and has
continued in excess of SERVO_TIME_TH. This is not
applicable for tight-shut or full-open actions, or when the period
specified by SERVO_TIME_TH is less than 0.
120
Temperature sensor failure
Temperature sensor failed
121
Pressure sensor failure
Pressure sensor failed,
122
Severe servo output drift
SERVO_OUTPUT_SIGNAL has reached 10% or 90%, and has
continued in excess of SERVO_TIME_TH. This is not
applicable for tight-shut or fullopen actions, or when the period
specified by SERVO_TIME_TH is less than 0.
123
Deviation error
The deviation between the setpoint and measured valve
position has exceeded DEVIATION_LIM continuously for the
period specified by DEVIATION_TIME_TH [2].
124
Position sensor failure
Position sensor failed
125
A/D converter failure
A/D converter failed
Summary of Contents for FVP110
Page 14: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 22: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 48: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 50: ...FVP 110 Fieldbus Valve Positioner Manual 34 GE Energy Block Diagram Figure 14 Block Diagram ...
Page 74: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 88: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 97: ...81 Dimensions Standard Specifications Dimensions Figure 46 Single Acting Actuator Dimensions ...
Page 99: ...83 Dimensions Standard Specifications Figure 48 Terminal Configuration ...
Page 100: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 115: ...99 View Object Configuration Table 11 View Object for Transducer Block continued ...
Page 117: ...101 View Object Configuration Table 18 View Object for AO Function Block ...
Page 119: ...103 View Object Configuration Table 20 View Object for OS Function Block ...
Page 121: ...105 View Object Configuration Table 22 View Object for Resource Block ...
Page 124: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 130: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 138: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 156: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 168: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 238: ...FVP 110 Fieldbus Valve Positioner Manual 222 GE Energy Table 72 LM Parameter Part List ...
Page 239: ...223 LM Parameter List Link Master Functions ...
Page 246: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 262: ...FVP 110 Fieldbus Valve Positioner Manual 246 GE Energy Table 85 Download Error Codes ...
Page 265: ...249 Comments on System Network Software Download Table 88 DOMAIN_DESCRIPTOR ...
Page 266: ...FVP 110 Fieldbus Valve Positioner Manual 250 GE Energy Table 89 DOMAIN_HEADER ...
Page 288: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 289: ...273 H Customer Maintenance Parts List ...
Page 290: ...FVP 110 Fieldbus Valve Positioner Manual 274 GE Energy ...
Page 291: ......