FVP 110 Fieldbus Valve Positioner Manual
142
GE Energy
Modes
The target mode for a DI function block can be set from three block modes: O/S, Auto,
and Man.
PV Value (PV_D)
A limit switch signal is transferred from the transducer block via a channel. Normally, the
Transducer Value and Transducer Status values in SIMULATE_D are copied to
FIELD_VAL_D, indicating the on/off status of the corresponding limit switch. If
SIMULATE_D is set to
Enable
, the Simulate Value and Simulate Status values in
SIMULATE_D are copied to FIELD_VAL_D.
SIMULATE_D contains the following data:
Simulate Status
Status to be set in simulation mode
Simulate Value
Value to be set in simulation mode
Transducer Status
Status of input from transducer
Transducer Value
Value of input from transducer
Enable/Disable
Whether to enable
2
or disable
1
simulation
The value of FIELD_VAL_D is copied to the process value PV_D. At this time, if the Invert
option (bit 0) is specified as true, the on/off status is inverted (Table 41).
Filtering
Transfer of a change in the value of FIELD_VAL_D to the value of PV_D can be delayed
for a desired time period set in the parameter PV_FTIME (in seconds).
Output
The value of the output OUT_D is generated based on the value of PV_D.
Table 41
FIELD_VAL_D
Value of
FIELD_VAL_D
Value of PV_D
Invert = False
Invert = True
0
0 (off)
1
≥
1
1 (on)
0
Summary of Contents for FVP110
Page 14: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 22: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 48: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 50: ...FVP 110 Fieldbus Valve Positioner Manual 34 GE Energy Block Diagram Figure 14 Block Diagram ...
Page 74: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 88: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 97: ...81 Dimensions Standard Specifications Dimensions Figure 46 Single Acting Actuator Dimensions ...
Page 99: ...83 Dimensions Standard Specifications Figure 48 Terminal Configuration ...
Page 100: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 115: ...99 View Object Configuration Table 11 View Object for Transducer Block continued ...
Page 117: ...101 View Object Configuration Table 18 View Object for AO Function Block ...
Page 119: ...103 View Object Configuration Table 20 View Object for OS Function Block ...
Page 121: ...105 View Object Configuration Table 22 View Object for Resource Block ...
Page 124: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 130: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 138: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 156: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 168: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 238: ...FVP 110 Fieldbus Valve Positioner Manual 222 GE Energy Table 72 LM Parameter Part List ...
Page 239: ...223 LM Parameter List Link Master Functions ...
Page 246: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 262: ...FVP 110 Fieldbus Valve Positioner Manual 246 GE Energy Table 85 Download Error Codes ...
Page 265: ...249 Comments on System Network Software Download Table 88 DOMAIN_DESCRIPTOR ...
Page 266: ...FVP 110 Fieldbus Valve Positioner Manual 250 GE Energy Table 89 DOMAIN_HEADER ...
Page 288: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 289: ...273 H Customer Maintenance Parts List ...
Page 290: ...FVP 110 Fieldbus Valve Positioner Manual 274 GE Energy ...
Page 291: ......