163
Measured-value Tracking
PID Function Block
Measured-value Tracking
Measured-value tracking, also referred to as SP-PV tracking, is the action of equalizing
the setpoint SP to the measured value PV when the block mode (MODE_BLK.actual) is
Man in order to prevent a sudden change in control output from being caused by a
mode change to Auto.
While a cascade primary control block is performing automatic control in Auto or Cas
mode, when the mode of its secondary control block is changed from Cas to Auto, the
cascade connection is opened and the control action of the primary block stops. The SP
of the primary controller can also be equalized to its cascade input signal CAS_IN in
this case.
The settings for measured-value tracking are made in the parameter CONTROL_OPTS
(Table 49).
CONTROL_OPTS
CONTROL_OPTS is a parameter that stipulates control options (Table 49).
Table 49
CONTROL_OPTS of PID Block
Bit
Options in CONTROL_OPTS
Description
0
Bypass Enable
Switch for activating the control action bypass
1
SP-PV Track in Man
Equalizes SP to PV when MODE_BLK.target is set to Man.
2
SP-PV Track in Rout
Equalizes SP to PV when MODE_BLK.target is set to ROut.
3
SP-PV Track in LO or IMan
Equalizes SP to PV when MODE_BLK.actual is set to LO or
IMan.
4
SP Track retained Target
Equalizes SP to RCAS_IN or CAS_IN when MODE_BLK.target
is either in IMan, LO, Man or ROut and MODE_BLK.actual is
set to RCas or Cas.
5
Direct Acting
Set the PID block to be a direct acting controller.
7
Track Enable
While this option is set, if the value of TRK_IN_D becomes
1
,
the mode transfers to LO.
8
Track in Manual
Set this option when the mode should be transferred to LO
even when MODE_BLK.target is set to Man. This option is
invalid when Track Enable option is not set.
9
Use PV for BKCAL_OUT
Sets the value of PV in BKCAL_OUT and RCAS_OUT, instead
of the value of SP.
Summary of Contents for FVP110
Page 14: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 22: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 48: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 50: ...FVP 110 Fieldbus Valve Positioner Manual 34 GE Energy Block Diagram Figure 14 Block Diagram ...
Page 74: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 88: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 97: ...81 Dimensions Standard Specifications Dimensions Figure 46 Single Acting Actuator Dimensions ...
Page 99: ...83 Dimensions Standard Specifications Figure 48 Terminal Configuration ...
Page 100: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 115: ...99 View Object Configuration Table 11 View Object for Transducer Block continued ...
Page 117: ...101 View Object Configuration Table 18 View Object for AO Function Block ...
Page 119: ...103 View Object Configuration Table 20 View Object for OS Function Block ...
Page 121: ...105 View Object Configuration Table 22 View Object for Resource Block ...
Page 124: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 130: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 138: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 156: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 168: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 238: ...FVP 110 Fieldbus Valve Positioner Manual 222 GE Energy Table 72 LM Parameter Part List ...
Page 239: ...223 LM Parameter List Link Master Functions ...
Page 246: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 262: ...FVP 110 Fieldbus Valve Positioner Manual 246 GE Energy Table 85 Download Error Codes ...
Page 265: ...249 Comments on System Network Software Download Table 88 DOMAIN_DESCRIPTOR ...
Page 266: ...FVP 110 Fieldbus Valve Positioner Manual 250 GE Energy Table 89 DOMAIN_HEADER ...
Page 288: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 289: ...273 H Customer Maintenance Parts List ...
Page 290: ...FVP 110 Fieldbus Valve Positioner Manual 274 GE Energy ...
Page 291: ......