FVP 110 Fieldbus Valve Positioner Manual
164
GE Energy
Initialization and Manual Fallback (IMan)
Initialization and manual fallback denotes a set of abnormality handling actions in which a
PID block changes mode to IMan (initialization manual) and suspends the control action.
Initialization and manual fallback takes place only when the following condition is met:
❑
The quality component of BKCAL_IN.status (data status of BKCAL_IN) is Bad.
OR
❑
The quality component of BKCAL_IN.status is Good (c)
AND
❑
The sub-status component of BKCAL_IN.status is FSA, LO, NI, or IR.
Manual Fallback
Manual fallback denotes an abnormality handling action in which a PID block changes
mode to Man (manual) and suspends the control action.
The manual fallback action is enabled to take place if the Target to Manual if BAD IN
option in STATUS_OPTS is set as true, and it takes place when the following condition is
met:
❑
IN.status (data status of IN) is Bad except when the control action bypass is on.
12
Obey SP limits if Cas or RCas Puts the setpoint high/low limits in force in the Cas or RCas
mode.
13
No OUT limits in Manual
Disables the high/low limits for OUT in the Man mode.
Table 49
CONTROL_OPTS of PID Block (Continued)
Bit
Options in CONTROL_OPTS
Description
Summary of Contents for FVP110
Page 14: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 22: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 48: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 50: ...FVP 110 Fieldbus Valve Positioner Manual 34 GE Energy Block Diagram Figure 14 Block Diagram ...
Page 74: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 88: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 97: ...81 Dimensions Standard Specifications Dimensions Figure 46 Single Acting Actuator Dimensions ...
Page 99: ...83 Dimensions Standard Specifications Figure 48 Terminal Configuration ...
Page 100: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 115: ...99 View Object Configuration Table 11 View Object for Transducer Block continued ...
Page 117: ...101 View Object Configuration Table 18 View Object for AO Function Block ...
Page 119: ...103 View Object Configuration Table 20 View Object for OS Function Block ...
Page 121: ...105 View Object Configuration Table 22 View Object for Resource Block ...
Page 124: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 130: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 138: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 156: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 168: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 238: ...FVP 110 Fieldbus Valve Positioner Manual 222 GE Energy Table 72 LM Parameter Part List ...
Page 239: ...223 LM Parameter List Link Master Functions ...
Page 246: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 262: ...FVP 110 Fieldbus Valve Positioner Manual 246 GE Energy Table 85 Download Error Codes ...
Page 265: ...249 Comments on System Network Software Download Table 88 DOMAIN_DESCRIPTOR ...
Page 266: ...FVP 110 Fieldbus Valve Positioner Manual 250 GE Energy Table 89 DOMAIN_HEADER ...
Page 288: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 289: ...273 H Customer Maintenance Parts List ...
Page 290: ...FVP 110 Fieldbus Valve Positioner Manual 274 GE Energy ...
Page 291: ......