Parameters of PID and PID2
Function Block Parameters
Parameters of PID and PID2 Blocks (Optional)
Table 65 lists the PID parameters for PID1. PID2 uses the same parameters but with a
starting
Index
of
8100
.
23
14023 UPDATE_EV
T
Shows the contents of an update event upon
occurrence.
24
14024 BLOCK_ALM
Shows the contents of a block alarm upon
occurrence.
Table 65
PID Block Parameters
Relative
Index
Index
Parameter
Name
Default
(factory
setting)
Write
Description
0
8000
Block Header
Block Tag
=O/S
Information about this block, including the
block tag, DD revision, execution time
1
8001
ST_REV
0
—
Incremented when a change is made to the
parameter settings for the PID block to indicate
the revision level of the settings, and used to
see whether there is a change in parameter
settings.
2
8002
TAG_DESC
Spaces
Universal parameter storing the description of
the tag.
3
8003
STRATEGY
1
Universal parameter used by an upper-level
system to classify the function blocks.
4
8004
ALERT_KEY
1
Universal parameter used as a key to identify
the point from which an alert is issued;
normally used by an upperlevel system to
select alerts to provide to a particular operator
who covers a specific area of the plant.
5
8005
MODE_BLK
O/S
Universal parameter that indicates the block
operation conditions and is composed of actual
mode, target mode, permitted modes, and
normal mode.
6
8006
BLOCK_ERR
—
—
Indicates the error statuses related to the block
itself.
Table 64
OS Block Parameters (Continued)
Relative
Index
Index
Parameter
Name
Default
(factory
setting)
Write
Description
Summary of Contents for FVP110
Page 14: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 22: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 48: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 50: ...FVP 110 Fieldbus Valve Positioner Manual 34 GE Energy Block Diagram Figure 14 Block Diagram ...
Page 74: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 88: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 97: ...81 Dimensions Standard Specifications Dimensions Figure 46 Single Acting Actuator Dimensions ...
Page 99: ...83 Dimensions Standard Specifications Figure 48 Terminal Configuration ...
Page 100: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 115: ...99 View Object Configuration Table 11 View Object for Transducer Block continued ...
Page 117: ...101 View Object Configuration Table 18 View Object for AO Function Block ...
Page 119: ...103 View Object Configuration Table 20 View Object for OS Function Block ...
Page 121: ...105 View Object Configuration Table 22 View Object for Resource Block ...
Page 124: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 130: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 138: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 156: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 168: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 238: ...FVP 110 Fieldbus Valve Positioner Manual 222 GE Energy Table 72 LM Parameter Part List ...
Page 239: ...223 LM Parameter List Link Master Functions ...
Page 246: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 262: ...FVP 110 Fieldbus Valve Positioner Manual 246 GE Energy Table 85 Download Error Codes ...
Page 265: ...249 Comments on System Network Software Download Table 88 DOMAIN_DESCRIPTOR ...
Page 266: ...FVP 110 Fieldbus Valve Positioner Manual 250 GE Energy Table 89 DOMAIN_HEADER ...
Page 288: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 289: ...273 H Customer Maintenance Parts List ...
Page 290: ...FVP 110 Fieldbus Valve Positioner Manual 274 GE Energy ...
Page 291: ......