229
FAQs
Link Master Functions
FAQs
Q1. When the LAS stops, a FVP does not back it up by becoming the LAS. Why?
A1-1. Is that FVP running as an LM? Check that the value of
BootOperatFunctionalClass (index 367) is 2 (indicating that it is an LM).
A1-2. Check the values of V(ST) and V(TN) in all LMs on the segment and confirm that
the following condition is met:
Q2. How can I make a FVP become the LAS?
A2-1. Check that the version numbers of the active schedules in the current LAS and
the FVP are the same by reading:
LinkScheduleListCharacteristicsRecord (index 374 for a FVP)
- ActiveScheduleVersion (subindex 3)
A2-2. Make the FVP declare itself as and become the LAS by writing:
❑
0x00 (false) to PrimaryLinkMasterFlagVariable in the current LAS; and
❑
0xFF (true) to PrimaryLinkMasterFlagVariable (index 364) in the FVP.
Q3. On a segment where a FVP works as the LAS, another device cannot be
connected. How come?
A3-1. Check the following bus parameters that indicate the bus parameter as being the
LAS for the FVP and the capabilities of being the LAS for the device that cannot be
connected:
❑
V(ST), V(MID), V(MRD) of FVP: ConfiguredLinkSettingsRecord (index 369)
❑
V(ST), V(MID), V(MRD) of problematic device: DlmeBasicInfo
Then, confirm that the following conditions are met:
A3-2. Check the node address of the problematic device is not included in the
V(FUN)+V(NUN) of the FVP.
FVP
Other LMs
V(ST) X V(TN)
<
V(ST) V(TN)
FVP
Problematic Device
V(ST)
>
V(ST)
V(MID)
>
V(MID)
V(MRD)
>
V(MRD)
Summary of Contents for FVP110
Page 14: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 22: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 48: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 50: ...FVP 110 Fieldbus Valve Positioner Manual 34 GE Energy Block Diagram Figure 14 Block Diagram ...
Page 74: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 88: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 97: ...81 Dimensions Standard Specifications Dimensions Figure 46 Single Acting Actuator Dimensions ...
Page 99: ...83 Dimensions Standard Specifications Figure 48 Terminal Configuration ...
Page 100: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 115: ...99 View Object Configuration Table 11 View Object for Transducer Block continued ...
Page 117: ...101 View Object Configuration Table 18 View Object for AO Function Block ...
Page 119: ...103 View Object Configuration Table 20 View Object for OS Function Block ...
Page 121: ...105 View Object Configuration Table 22 View Object for Resource Block ...
Page 124: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 130: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 138: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 156: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 168: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 238: ...FVP 110 Fieldbus Valve Positioner Manual 222 GE Energy Table 72 LM Parameter Part List ...
Page 239: ...223 LM Parameter List Link Master Functions ...
Page 246: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 262: ...FVP 110 Fieldbus Valve Positioner Manual 246 GE Energy Table 85 Download Error Codes ...
Page 265: ...249 Comments on System Network Software Download Table 88 DOMAIN_DESCRIPTOR ...
Page 266: ...FVP 110 Fieldbus Valve Positioner Manual 250 GE Energy Table 89 DOMAIN_HEADER ...
Page 288: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 289: ...273 H Customer Maintenance Parts List ...
Page 290: ...FVP 110 Fieldbus Valve Positioner Manual 274 GE Energy ...
Page 291: ......