257
Moderate Response with a Flat
Manual Tuning Guideline
❑
If necessary, decrease the value for SERVO_GAIN to 2/3 or 1/2 of the originally
entered value.
❑
If necessary, set the SERVO_DEADBAND. Set a value in approximately the
range of a limit cycle (recommended upper limit is 2%).
❑
If the limit cycle is not eliminated, check the piping and feedback lever installation
by referring to Section 18.4.
Modifying Overshoot
❑
Increase the value for SERVO_RATE to reduce an excessively rapid response.
Verify the 10% step response and increment the value by 0.2.
❑
If necessary, increment the value for SERVO_RESET by 5.
❑
The same boost value is set on both the air delivery and exhaust sides by Auto
Tuning. If the overshoot on the exhaust side is larger than that on the air delivery
side for a double-acting model, input a negative value in X_BOOST_VALUE [1]
[2], without changing the value of 0 in X_BST_ON_THRESHOLD [1] [2] and
X_BST_OFF_THRESHOLD [1] [2]. First, try to input a negative value of half that
of BOOST_VALUE [1] [2], and if necessary, increment or decrement the value by
1.
Improving the Stabilization Time and Slow Overshoot
Decrease the value for SERVO_RESET to improve the capability of tracking the target
value. However, if the value is too small, the hunting operation or limit cycle may occur.
Verify the 10% step response and decrement the value by 2 to 3.
Improving the Response Time
❑
Increment or decrement the value for BOOST_VALUE [1] [2] and
X_BOOST_VALUE [1] [2] by 2, respectively.
❑
If necessary, increment the value for SERVO_GAIN by 30.
Checking Hunting Operation
Input a value in a large step of approx. 80% to ensure the hunting operation does not
occur. If the hunting operation does occur,:
1. Decrease the value for SERVO_GAIN to 2/3 or 1/2 of the originally entered value.
2. Increase the value for SERVO_RESET by approx. 1.5 times.
After tuning the control parameters, re-check each parameter if necessary.
Summary of Contents for FVP110
Page 14: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 22: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 48: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 50: ...FVP 110 Fieldbus Valve Positioner Manual 34 GE Energy Block Diagram Figure 14 Block Diagram ...
Page 74: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 88: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 97: ...81 Dimensions Standard Specifications Dimensions Figure 46 Single Acting Actuator Dimensions ...
Page 99: ...83 Dimensions Standard Specifications Figure 48 Terminal Configuration ...
Page 100: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 115: ...99 View Object Configuration Table 11 View Object for Transducer Block continued ...
Page 117: ...101 View Object Configuration Table 18 View Object for AO Function Block ...
Page 119: ...103 View Object Configuration Table 20 View Object for OS Function Block ...
Page 121: ...105 View Object Configuration Table 22 View Object for Resource Block ...
Page 124: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 130: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 138: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 156: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 168: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 238: ...FVP 110 Fieldbus Valve Positioner Manual 222 GE Energy Table 72 LM Parameter Part List ...
Page 239: ...223 LM Parameter List Link Master Functions ...
Page 246: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 262: ...FVP 110 Fieldbus Valve Positioner Manual 246 GE Energy Table 85 Download Error Codes ...
Page 265: ...249 Comments on System Network Software Download Table 88 DOMAIN_DESCRIPTOR ...
Page 266: ...FVP 110 Fieldbus Valve Positioner Manual 250 GE Energy Table 89 DOMAIN_HEADER ...
Page 288: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 289: ...273 H Customer Maintenance Parts List ...
Page 290: ...FVP 110 Fieldbus Valve Positioner Manual 274 GE Energy ...
Page 291: ......