259
Description of Control Parameters
Manual Tuning Guideline
Description of Control Parameters
The FVP110's basic method of controlling the valve position is PI-D control. This control
is characterized by the fact that a rapid output change is prevented by the derivative
term of D being added to the feedback.
In addition, FVP110 has a boost function that serves as an output acceleration function
after an input change, because it compensates the nonlinearity caused by the structure
of a valve or FVP.
When you set these parameters, change the mode of the transducer block and AO
function block to O/S.
SERVO_GAIN
Tuning range: 0.1 to 1300 (Default: 120)
Set the loop gain of PI-D control.
The proportional gain of PI-D control increases in proportion to (SERVO_GAIN /
INTERNAL_GAIN).
If you increase the value for SERVO_GAIN, tracking capability tends to increase,
whereas control stability tends to decrease.
SERVO_RESET
Tuning range: 0, 2 to 50 sec (Default: 15 sec)
Set the integral time of PI-D control.
The pace of change in integral volume quickens in reverse proportion to the integral
time and the volume changes repeatedly until the deviation disappears.
If you set a:
❑
Smaller value for the integral time, the deviation disappears more quickly,
whereas fast accumulation of integral components may cause an overshoot.
❑
Larger value for the integral time, you can reduce the accumulation of excessive
integral components when the deviation is large, but it takes longer for the
deviation to disappear.
❑
0, this function is invalid.
Summary of Contents for FVP110
Page 14: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 22: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 48: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 50: ...FVP 110 Fieldbus Valve Positioner Manual 34 GE Energy Block Diagram Figure 14 Block Diagram ...
Page 74: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 88: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 97: ...81 Dimensions Standard Specifications Dimensions Figure 46 Single Acting Actuator Dimensions ...
Page 99: ...83 Dimensions Standard Specifications Figure 48 Terminal Configuration ...
Page 100: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 115: ...99 View Object Configuration Table 11 View Object for Transducer Block continued ...
Page 117: ...101 View Object Configuration Table 18 View Object for AO Function Block ...
Page 119: ...103 View Object Configuration Table 20 View Object for OS Function Block ...
Page 121: ...105 View Object Configuration Table 22 View Object for Resource Block ...
Page 124: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 130: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 138: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 156: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 168: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 238: ...FVP 110 Fieldbus Valve Positioner Manual 222 GE Energy Table 72 LM Parameter Part List ...
Page 239: ...223 LM Parameter List Link Master Functions ...
Page 246: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 262: ...FVP 110 Fieldbus Valve Positioner Manual 246 GE Energy Table 85 Download Error Codes ...
Page 265: ...249 Comments on System Network Software Download Table 88 DOMAIN_DESCRIPTOR ...
Page 266: ...FVP 110 Fieldbus Valve Positioner Manual 250 GE Energy Table 89 DOMAIN_HEADER ...
Page 288: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 289: ...273 H Customer Maintenance Parts List ...
Page 290: ...FVP 110 Fieldbus Valve Positioner Manual 274 GE Energy ...
Page 291: ......