23
CENELEC ATEX (KEMA)
Safety
Cable
The cable used to interconnect the devices needs to comply with the following
parameters:
❑
Loop resistance R': 15 to 150
Ω
/km
❑
Inductance per unit length L': 0.4 to 1 mH/km
❑
Capacitance per unit length C': 80 to 200 nF/km
C' = C' line/line + 0.5 C' line/screen, if both lines are floating
or
C' = C' line/line + C' line/screen, if the screen is connected to one line
length of spur cable: max. 30 m (EEx ia IIC T4) or 120 m (EEx ia IIB T4)
length of trunk cable: max. 1 km (EEx ia IIC T4) or 1.9 km (EEx ia IIB T4)
Terminators
The terminator must be certified by a notified body as FISCO model and at each end of
the trunk cable an approved line terminator with the following parameters is suitable:
R = 90 to 100
Ω
C = 0 to 2.2
μ
F
The resistor must be infallible according to EN 50020. One of the two allowed
terminators might already be integrated in the associated apparatus (bus supply unit).
Field Instruments
Descriptions and Intrinsically safe ratings of the positioner (FIELD INSTRUMENTS) are
as follows:
Ambient Temperature: –40 to 60 °C
Enclosure: IP65
Electrical parameters:
❑
EEx ia IIC T4
❑
Maximum Voltage (Ui) = 17.5 V
❑
Maximum Current (Ii) = 360 mA
❑
Maximum Power (Pi) = 2.52 W
❑
Internal Capacitance (Ci) = 1.76 nF
❑
Internal Inductance (Li) = 0
μ
H
Summary of Contents for FVP110
Page 14: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 22: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 48: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 50: ...FVP 110 Fieldbus Valve Positioner Manual 34 GE Energy Block Diagram Figure 14 Block Diagram ...
Page 74: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 88: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 97: ...81 Dimensions Standard Specifications Dimensions Figure 46 Single Acting Actuator Dimensions ...
Page 99: ...83 Dimensions Standard Specifications Figure 48 Terminal Configuration ...
Page 100: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 115: ...99 View Object Configuration Table 11 View Object for Transducer Block continued ...
Page 117: ...101 View Object Configuration Table 18 View Object for AO Function Block ...
Page 119: ...103 View Object Configuration Table 20 View Object for OS Function Block ...
Page 121: ...105 View Object Configuration Table 22 View Object for Resource Block ...
Page 124: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 130: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 138: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 156: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 168: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 238: ...FVP 110 Fieldbus Valve Positioner Manual 222 GE Energy Table 72 LM Parameter Part List ...
Page 239: ...223 LM Parameter List Link Master Functions ...
Page 246: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 262: ...FVP 110 Fieldbus Valve Positioner Manual 246 GE Energy Table 85 Download Error Codes ...
Page 265: ...249 Comments on System Network Software Download Table 88 DOMAIN_DESCRIPTOR ...
Page 266: ...FVP 110 Fieldbus Valve Positioner Manual 250 GE Energy Table 89 DOMAIN_HEADER ...
Page 288: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 289: ...273 H Customer Maintenance Parts List ...
Page 290: ...FVP 110 Fieldbus Valve Positioner Manual 274 GE Energy ...
Page 291: ......