Camflex Rotary Valve Mounting
Installing the FVP110 on the
1. Turn the A/M selector switch clockwise to
M
Figure 26
A/M Selector Switch
2. Vary the pneumatic pressure output to the valve actuator by changing the regulator
output pressure by more than 70 kPa (approximately), regardless of the input signal
of the FVP110. For an FVP110 equipped with pressure gauges, you can read the
output pressure to the actuator.
When using the Double Acting Type, the pneumatic pressure can only be varied
from
OUT1
to the valve actuator. The pressure is always 0% from
OUT2
to the
valve actuator. The valve position is not always in accord with the regulator
pressure.
3. Turn the A/M selector switch counterclockwise until the stopper pin touches the side
of the FVP110’s casing to ensure the switch position changes to
A
.
Camflex Rotary Valve Mounting
This section describes the procedure for mounting the FVP on rotary control valves,
using GE Masoneilan rotary valves as an example. Refer to Figure 27 on page 44 and
Figure 28 on page 45 for details.
Tools Required
❑
5/32 and 3/16" Hex Wrench with tee handle
❑
3 mm, 4 mm, and 5mm Hex Wrench
❑
7/16" Combination Wrench
The mounting bracket for the Camflex
*
has four sides, two square and two rectangular.
One square side has a large hole in the center with four smaller holes above, below, left
and right of the center hole; this side mounts to the actuator.
The other square side has a large hole that is a little bit off center and two rows of two
smaller holes above and below the large hole; this side mounts to the FVP.
Summary of Contents for FVP110
Page 14: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 22: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 48: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 50: ...FVP 110 Fieldbus Valve Positioner Manual 34 GE Energy Block Diagram Figure 14 Block Diagram ...
Page 74: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 88: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 97: ...81 Dimensions Standard Specifications Dimensions Figure 46 Single Acting Actuator Dimensions ...
Page 99: ...83 Dimensions Standard Specifications Figure 48 Terminal Configuration ...
Page 100: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 115: ...99 View Object Configuration Table 11 View Object for Transducer Block continued ...
Page 117: ...101 View Object Configuration Table 18 View Object for AO Function Block ...
Page 119: ...103 View Object Configuration Table 20 View Object for OS Function Block ...
Page 121: ...105 View Object Configuration Table 22 View Object for Resource Block ...
Page 124: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 130: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 138: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 156: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 168: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 238: ...FVP 110 Fieldbus Valve Positioner Manual 222 GE Energy Table 72 LM Parameter Part List ...
Page 239: ...223 LM Parameter List Link Master Functions ...
Page 246: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 262: ...FVP 110 Fieldbus Valve Positioner Manual 246 GE Energy Table 85 Download Error Codes ...
Page 265: ...249 Comments on System Network Software Download Table 88 DOMAIN_DESCRIPTOR ...
Page 266: ...FVP 110 Fieldbus Valve Positioner Manual 250 GE Energy Table 89 DOMAIN_HEADER ...
Page 288: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 289: ...273 H Customer Maintenance Parts List ...
Page 290: ...FVP 110 Fieldbus Valve Positioner Manual 274 GE Energy ...
Page 291: ......