FVP 110 Fieldbus Valve Positioner Manual
94
GE Energy
Setting of Tags and Addresses
To set PD Tags and node addresses in the FVP110:
1. Connect the FVP110 with other network devices and turn on the power of the host
and the bus.
There are three states of Fieldbus devices (Figure 54), and if the state is other than
the lowest SM_OPERATIONAL state, no function block is executed.
2. Transfer the FVP110 to the operational state when a tag or address is changed.
Figure 54
Status Transition by Setting PD Tag and Node Address
FVP110 has a PD Tag (CV1001) and node address (247, or hexadecimal 0xF7) that
are set upon shipment from the factory, unless otherwise specified. If two FVP110s
are connected at a time, one FVP110 keeps the shipment address, while the other
has a default address (See Figure 52).
3. To:
❑
Change only the node address, clear the address once and then set a new node
address.
❑
Set the PD Tag, first clear the node address and clear the PD Tag, then set the PD
Tag and node address again.
Devices whose node address was cleared await the default address (randomly
chosen from a range of 248 to 251, or from hexadecimal 0xF8 to 0xFB).
4. Specify the device ID in order to correctly specify the device. The device ID of the
FVP110 is
4456440001xxxxxxxx
or
4456440007xxxxxxxx
. The
xxxxxxxx
at the end of
the device ID is a total of 8 alphanumeric characters.
Summary of Contents for FVP110
Page 14: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 22: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 48: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 50: ...FVP 110 Fieldbus Valve Positioner Manual 34 GE Energy Block Diagram Figure 14 Block Diagram ...
Page 74: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 88: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 97: ...81 Dimensions Standard Specifications Dimensions Figure 46 Single Acting Actuator Dimensions ...
Page 99: ...83 Dimensions Standard Specifications Figure 48 Terminal Configuration ...
Page 100: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 115: ...99 View Object Configuration Table 11 View Object for Transducer Block continued ...
Page 117: ...101 View Object Configuration Table 18 View Object for AO Function Block ...
Page 119: ...103 View Object Configuration Table 20 View Object for OS Function Block ...
Page 121: ...105 View Object Configuration Table 22 View Object for Resource Block ...
Page 124: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 130: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 138: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 156: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 168: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 238: ...FVP 110 Fieldbus Valve Positioner Manual 222 GE Energy Table 72 LM Parameter Part List ...
Page 239: ...223 LM Parameter List Link Master Functions ...
Page 246: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 262: ...FVP 110 Fieldbus Valve Positioner Manual 246 GE Energy Table 85 Download Error Codes ...
Page 265: ...249 Comments on System Network Software Download Table 88 DOMAIN_DESCRIPTOR ...
Page 266: ...FVP 110 Fieldbus Valve Positioner Manual 250 GE Energy Table 89 DOMAIN_HEADER ...
Page 288: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 289: ...273 H Customer Maintenance Parts List ...
Page 290: ...FVP 110 Fieldbus Valve Positioner Manual 274 GE Energy ...
Page 291: ......