Simulation Function
Actions of the FVP110 During
Simulation Function
The FVP110 has a function to simulate input signals to its internal function blocks to
make the blocks to carry out the specified actions to allow for testing applications in the
host computer or alarm handling processes. Each function block has a parameter to
switch on/off the simulation function. To prevent this parameter setting from being
modified during plant operation by mistake, a hardware switch labeled SIM.ENABLE is
provided on the FVP110’s amplifier assembly (Figure 55).
To engage this function:
❑
Slide the switch position to
ON
.
or
❑
Remotely write
REMOTE LOOP TEST SWITCH
to
SIM_ENABLE_MSG
.
However, the value of SIM_ENABLE_MSG is lost when the power to the FVP110
is turned off.
When the simulation can be carried out, alarms generated from the resource blocks
mask the other device alarms. Hence, simulation must be disabled immediately after it
has finished.
Figure 55
SIM.ENABLE Switch
9
9
Value
Value of the related data
10
10
Relative Index
Relative Index to the related data
8
Static Revision
Value of ST_REV in the block
11
11
9
Unit Index
Unit code of the related data
Table 28
Alert Objects (Continued)
Subindex
Parameter
Name
Description
Analog
Alert
Discrete
Alert
Update
Alert
Summary of Contents for FVP110
Page 14: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 22: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 48: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 50: ...FVP 110 Fieldbus Valve Positioner Manual 34 GE Energy Block Diagram Figure 14 Block Diagram ...
Page 74: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 88: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 97: ...81 Dimensions Standard Specifications Dimensions Figure 46 Single Acting Actuator Dimensions ...
Page 99: ...83 Dimensions Standard Specifications Figure 48 Terminal Configuration ...
Page 100: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 115: ...99 View Object Configuration Table 11 View Object for Transducer Block continued ...
Page 117: ...101 View Object Configuration Table 18 View Object for AO Function Block ...
Page 119: ...103 View Object Configuration Table 20 View Object for OS Function Block ...
Page 121: ...105 View Object Configuration Table 22 View Object for Resource Block ...
Page 124: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 130: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 138: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 156: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 168: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 238: ...FVP 110 Fieldbus Valve Positioner Manual 222 GE Energy Table 72 LM Parameter Part List ...
Page 239: ...223 LM Parameter List Link Master Functions ...
Page 246: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 262: ...FVP 110 Fieldbus Valve Positioner Manual 246 GE Energy Table 85 Download Error Codes ...
Page 265: ...249 Comments on System Network Software Download Table 88 DOMAIN_DESCRIPTOR ...
Page 266: ...FVP 110 Fieldbus Valve Positioner Manual 250 GE Energy Table 89 DOMAIN_HEADER ...
Page 288: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 289: ...273 H Customer Maintenance Parts List ...
Page 290: ...FVP 110 Fieldbus Valve Positioner Manual 274 GE Energy ...
Page 291: ......