Model
GE-200A
Main Breaker
200 amp Horizontal throw left (off) to right (on)
Generator Breaker
Top right side 2 positions
WARNING
Only qualified personnel should be working on the panel box
An amateur should
NEVER
open the panel box
Please follow all rules and regulations of the National Electric Code
Step 1: Disassemble the interlock. Place the bottom plate (holes only) above the top right breaker and mark
holes. Plate is parallel to top right breaker.
Step 2: Turn off main breaker and remove panel cover.
Step 3: Drill holes as marked on panel cover with supplied 3/16 drill bit and remove all burs from drilling cover.
Step 4: Insert screws from rear of cover, install bottom plate, and install top plate (slotted) install thread lock to
screws and install retaining nuts. Ensure proper movement.
Step 5: Install 2 pole Generator breaker on top right side and place Generator Warning Sticker on Generator
breaker.