background image

 

 

Model

 

GE-200A  

Main Breaker

 

200 amp Horizontal throw left (off) to right (on)  

Generator Breaker

 

Top right side 2 positions 

 

    

 

WARNING 

Only qualified personnel should be working on the panel box 

An amateur should 

NEVER

 open the panel box 

Please follow all rules and regulations of the National Electric Code

 

 

Step 1: Disassemble the interlock. Place the bottom plate (holes only) above the top right breaker and mark 

holes.  Plate is parallel to top right breaker. 

 

 

 
Step 2: Turn off main breaker and remove panel cover.  
 
Step 3: Drill holes as marked on panel cover with supplied 3/16 drill bit and remove all burs from drilling cover. 
 
Step 4: Insert screws from rear of cover, install bottom plate, and install top plate (slotted) install thread lock to 

screws and install retaining nuts. Ensure proper movement. 

 

Step 5: Install 2 pole Generator breaker on top right side and place Generator Warning Sticker on Generator 

breaker. 

Reviews: