Electronic Temperature Control Systems 

)

 
 
 
 
 
 
 

 
 
 
 
 

DESCRIPTION

  

The VCPL series is especially designed for 
use in the commercial refrigeration and is 
available in various different models. The 
VCPL is also available with communication 
properties.

 

In addition to extremely accurate temperature 
control the VCPL offers the user diagnostics,  
marketing information and current statistics 
scroll i.e. average temperature, lowest 
temperature, highest temperature, number of 
door openings, compressor cycles and 
compressor running hours. 
As standard all models in the VCPL series are 
fitted with 6 relays switching : compressor, 
heating element or solenoid valve, external 
alarm,  evaporator fan, on/off switch and 
light(s). All relays in this unit have a switching 
capacity of 16 Amp. @ 240 Volt. 

 

WARNING 

This manual is part of the product and should be kept 
near the instrument for quick reference. 
The instrument should not be used for purposes other 
than described and/or specified by the manufacturer. 
These controls can only be used with GE double 
insulated sensors. 

 

SAFETY PRECAUTIONS

 

Ensure that the supply voltage is correct before 
connecting the instrument. (240 Volt ) 
Ensure that the instrument is not exposed to water or 
any other liquid. 
Ensure that the current that is switched does not 
exceed the maximum switching capacity of the 
instrument. If the  current to be switched is greater 
than the instrument limits, a separate relay should be 
installed. 
Ensure that all wires are properly connected in the 
appropriate terminal, a loose wire could cause 
sparking and damage the instrument and may be 
dangerous. 

 

BUTTON COMMANDS

 

 

 

 

TO SET THE TEMPERATURE

 

In case of an instrument failure or faulty functioning 
of the instrument, return it to your local distributor or 
direct to the manufacturer. If the unit is still in its 
warranty period it will be replaced free of charge. 
To set the temperature push the ‘temperature set 
button
’ and the display will intermittently show the 
letters SP (set point) and the pre-set temperature. To 
increase the temperature use the value up button (

), 

to decrease the temperature use the value down 
button (v). 
Once the required temperature is selected, release the 
buttons and wait until the display shows the actual 
temperature again. The instrument has now adopted 
the new setting and will operate in accordance with 
these new instructions. 

 

ACTIVATE A MANUAL 

DEFROST CYCLE

 

It may be possible that from time to time the user 
wants to use some extra defrost cycle(s). To activate 
a manual defrost, push the manual defrost button and 
keep it pressed for a minimum of 5 sec. Until the 
defrost signal shows on the display. 
A manual defrost may be activated as many times as 
required. 

 

WARNING SIGNALS 

In addition to its standard control functions, the GE-
VCPL series also contains a number of diagnostic 
functions and can show the following alarm signals: 
RSF – There is a refrigeration system failure. 

 

Contact your supplier. 

 

EE – There is a microprocessor (electronic) failure, 
contact your supplier. 

 

  PF1 – There is a sensor failure that is very likely 
caused by a loose connection of the sensor wire in 
the terminal block of the instrument. This sensor is 
the appliance sensor. Contact your local supplier. 

 

PF2 – There is a sensor failure (as PF1), but in the 
sensor of the evaporator. 

 

PF3 -  As PF1 and PF2 but this is the sensor 
connected to the condenser 

 

AL1 – The temperature of the appliance has 
exceeded its maximum allowable temperature. 

 

AL2 – The temperature of the appliance has 
exceeded the minimum allowable temperature. 

 

HT – The condenser is blocked 

 

CHANGING PARAMETER VALUES 

To change the parameter values switch the power to 
the unit off, push the temperature set button and keep 
it pushed whilst switching the power on again. The 
display will flash and intermittently show the figures 
888. Once the display stops flashing, the instrument 
is in parameter mode and the values can now be 
changed. 
To scroll through the parameters push the 
temperature set button and to change the value of the 
parameters use the ‘value’ buttons. 
When finished, release all buttons and wait until the 
display shows the actual temperature again. 

Please note that the VCPL has two different 
sets of parameters. The first batch can be 
accessed as described above and the second 
set can be accessed by holding the set button 

and the up button pushed together

WARNING 

If the power to the unit is switched off whilst the 
instrument is still in parameter mode, the system will 
NOT accept the changes. 

 

MAINTENANCE 

The GE-VCPL does NOT require any maintenance. 
WARNING 
To clean the facia of the GE-VCPL use wet soapy 
rag. 
The instrument is an electronic device, do not use 
water or any other cleaning liquid to clean the facia 
of the instrument as this may cause serious and 
unnecessary damage to the system and may be 
dangerous. 

 

WIRING INSTRUCTIONS 

All wiring instructions are printed on the housing of 
the unit and contain all possible information needed 
to connect the GE-VCPL 
Follow these instructions and ensure that all 
connections in the terminals of the instrument are 
properly fastened as loose connections may influence 
the performance of the instrument and may cause 
sparking. 
The GE-VCPL is powered by 240 Volt and should be 
connected direct to the mains. 
IMPORTANT 
Only authorised and competent personnel should 
connect and/or disconnect the GE-VCPL. 

INSTALLATION 

The recommended hole size for the GE-VCPL is 9 
5/32” x 3 5/8”but in addition there are the holes for 
the fasteners as per the drawing  on the reverse of 
this instruction manual. 

 

PARAMETER LISTING 

Access through set button: 
Param. Description 

Range

 

US 

Upper SP limit 

-40/212°F 

LS Lower 

SP 

limit 

-40/212°F 

DIF Differential 

1.8/178°F 

CA1 

Sensor 1 calibr. 

±17.8°F 

CA2 

Sensor 2 calibr. 

±17.8°F 

D1 

Display stability 

1 to 8 

D2 

Display speed 

1 to 255 

rt 

Min. rest time 

1 to 30 min 

dE 

Defrost intervals 

1 to 199 hrs 

dd 

Defrost duration 

1 to 199 min 

dF 

Defrost method 

1 = off 
2 = heater 
3 = hot gas 

dt 

Max temp. in 
appliance during 
defrost 

-40/212°F 

SP2 Max. 

evap. 

Temp. 

during defrost 

-40/212°F 

FP Fan 

stop 

during 

defrost 

0 = no 
1 = yes 

Fd 

Fan delay  to on 

0 – 60 min. 

CT Refr. 

System 

failure elapse time 

1 to 255 hrs 

dEF Display 

during 

defrost 

0 = temp. 
1 = start 
temp. 
2 = dEF 

LL 

Low alarm temp. 

-40/212°F 

HL High 

temp. 

alarm 

-40/212°F 

AD Alarm 

delay  0 

– 255 min. 

B1 

Buzzer off for 

0 to 255 min 

B2 

Buzzer on for  

0 – 255 min 

 

Access through set and up button 

 

Ht Blocked 

condenser temp. 

176 to 250°F 

St Time 

zone 

for 

reset 

1 to 255 hrs 

CF 

Degr C or F 

0 = C 
1 = F 

db 

Display brightness 

0 = bright 
1 = dim 

C1 Computer 

interface 

0 = wireless 
1 = Infra Red 

D1 Data 

intervals 1 

– 255 

minutes 

FL Compressor 

run 

after failure 

0 = yes 
1 = no 

 

 

 

cURus Approval Pending 

 

GE Electronic Temperature Control Systems should not be 
exposed to low temperatures or high humidity, such as 
outdoor or refrigerated environments. It is the customer’s 
responsibility to 
determine the proper application of the 
controls and to specify the optional Conformal Coating if the 
controls are going to be used in these 
environments. 