8
03 Product Introduction
User Manual
V1.0-2023-10-30
Power cable
Signal cable
No�
Parts
Description
1
PV string
The PV string consists PV panels series connected.
2
Inverter
Supports GEH 15 -30kW series inverters.
3
Battery
The battery used with the inverter shall be approved by the inverter
manufacturer. The approved battery list can be obtained through the official
website.
4
Battery breaker
Recommended specifications: nominal current≥63A, nominal
voltage≥1000V.
5
Load Breaker
Depend on the actual using load.
6
AC circuit
breaker and
bypass switch
Recommended specifications:
•
GEH15-3U-10: nominal current≥32A, nominal voltage≥400V
•
GEH20-3U-10: nominal current≥40A, nominal voltage≥400V
•
GEH25-3U-10: nominal current≥50A, nominal voltage≥400V
•
GEH29.9-3U-10/GEH30-3U-10: nominal current≥63A, nominal
voltage≥400V
7
Smart meter
The smart meter is delivered with the inverter or purchased from the
inverter manufacturer. Recommended model: GM3000.
8
BACK-UP
loads
•
Connecting BACK-UP loads, such as loads requiring 24-hour power
supply or other important loads.
• Connecting unbalanced loads. L1, L2, L3 of the inverter respectively
connected to loads with different power.
• Do not connect three-phase motor loads without N wires.
• Do not connect auto-coupling or isolation transformers.
1
BACK-UP load
4
6
8
3
7
2
6
5
Utility meter Utility grid
PV string
Battery
Battery breaker
ON-GRID
BACK-UP
Smart
Meter
AC circuit
breaker
Inverter
ON-GRID load
Load breaker
Bypass switch
CT
6
Single Inverter