![background image](http://html.mh-extra.com/html/ge/gek-106273l/gek-106273l_instruction-manual_134819138.webp)
RELAY COMMISSIONING
GEK-106273L
MIF Digital Feeder Protection
9-11
9.18.7. DEFINITE
TIME
•
Set the relay as follows:
51N Settings Group
Curve DEFINITE
TIME
Definite Time Delay
1.0
•
Apply 0.9 times the pickup current at the ground terminals and the relay should not trip.
•
Apply 1.1 times the pickup current and the relay should trip in 1.0 sec. Acceptable time range is between 1.00 and
1.06 sec.
•
Apply 4 times the pickup current and the relay should trip in 1.0 sec. Acceptable time range is between 1.00 and
1.06
sec.