RELAY COMMISSIONING
9-14
MIF Digital Feeder Protection
GEK-106273L
ENERVISTA MII
SETUP
HMI
USER
VALUE
RANGE
STEP
Phase IOC Low
Setting
50PL Function
F50PL
50PL Permission to Trip 50PL Trip Permission TRIP 50PL
Y/N
NA
50PL Tap / Pickup
50PL Pickup
TAP 50PL
0.1 – 30 In (Ph)
0.1 In (Ph)
50PL Time Delay
50PL Time Delay
TIME
0 – 600.00 s.
0.01 s.
Ground IOC High Set.
50NH Function
F50NH
50NH Permission to
50NH Trip Permission
TRIP
Y/N
NA
50NH Tap / Pickup (1/5
A ground)
50NH Pickup
TAP 50NH
0.1 – 30 In (Gnd)
0.1 In (G)
50NH Tap / Pickup
(sensitive ground)
50NH Pickup
TAP 50NH
0.005-0.12 A
0.001 A
50NH Time Delay
50NH Time Delay
TIME
0 – 600.00 s.
0.01 s.
Ground IOC Low
Setting
50NL Function
F50NL
50NL Permission to Trip 50NL Trip Permission TRIP 50NL
Y/N
NA
50NL Tap / Pickup (1/5
A ground)
50NL Pickup
TAP 50NL
0.1 – 30 In (Gnd)
0.1 In (G)
50NL Tap / Pickup
(sensitive ground)
50NL Pickup
TAP 50NL
0.005-0.12 A
0.001 A
50NL Time Delay
50NL Time Delay
TIME
0 – 600.00 s.
0.01 s.
Thermal Image (49)
49 Function
F49
Permission to Trip
49 Trip Permission
TRIP 49
Y/N
NA
49 Tap / Pickup
49 Pickup
TAP 49
0.1 – 2.4 In (Ph)
0.01 In (Ph)
Overload Percent Alarm
49 Alarm Level
ALARM 49
70% – 100% ITH
Heating Time Constant
T1
T1
3 – 600 min.
1 min
Cooling Time Constant
T2 T2
1 – 6 times
τ
1
1
Summary of Contents for GEK-106273L
Page 19: ...GETTING STARTED 1 12 MIF Digital Feeder Protection GEK 106273L ...
Page 95: ...SETTINGS 5 38 MIF Digital Feeder Protection GEK 106273L ...
Page 101: ...I O CONFIGURATION 6 44 MIF Digital Feeder Protection GEK 106273L ...
Page 127: ...KEYPAD AND DISPLAY 8 26 MIF Digital Feeder Protection GEK 106273L ...
Page 147: ...INSTALLATION AND MAINTENANCE 10 2 MIF Digital Feeder Protection GEK 106273L ...
Page 199: ...ANNEX 5 HARMONIC FILTERING 15 4 MIF Digital Feeder Protection GEK 106273L ...