5.3. ADVANCED SETTINGS
5 SETTINGS
4-14
MIF Digital Feeder Protection
GEK-106273L
4.4.2. EVENT
RECORDER
Actual – Event Recorder
option makes the last 24 relay events to be retrieved (up to 32) and displayed in the
window appearing in Figure 4-16. Each event record is labeled with date, time (with 1msec. resolution), the cause of
the event (pickup, trip of a certain function, etc.), and a list of the status of all inputs, outputs and functions during the
event. Additionally, the program also shows current and voltage values for all phases and ground, frequency and
single line sequence voltage during the event.
FIGURE 4-16. EVENTS WINDOW
The retrieved events can be reviewed in this window or also saved to disk (to be opened with ENERVISTA MII
SETUP program) or exported to CSV (Comma Separated Values) format. This is a standard text table format that can
be opened with most commercially available database or spreadsheet programs such as MS Access or Excel.