background image

03

04

3 Product Introduction

3.1 Intended Usage 

The GEP series which is a Three or Six MPPT,  three phase transformer-less grid-connected 
inverter which is a crucial unit between the PV string and the utility grid in the PV power system.
Inverter is dedicated to converting directing current generated by the PV module into alternating
current, and feeding it into the utility grid, this conforms to parameters of the local utility grid. The
intended usage of inverter is illustrated in the below figure.

  

kW.H

A

B

C

D

 

GEP series 
GEP12-L-10,GEP15-L-10,GEP20-L-10,GEP25-10,GEP30-10,GEP36-10,GEP29.9-10,GEP30-L-1
0,GEP35-L-10,GEP50-10,GEP60-10 support four different types(TN-S,TN-C,TN-C-S, TT) of grid. 
please refer to the below figure. 

The reason why the inverter can't be connected to the PV module is that the positive or 
negative terminal should be grounded, except when a transformer has been used between 
the inverter and grid.

Item

A

B

C

D

Description

PV string

Inverter

Meter device

Utility grid

Note

Monocrystalline silicon, polycrystalline silicon and others.

GEP Series

Meter cupboard with distributed generation system

TN-S, TN-C, TN-C-S, TT, IT

(different Model types with different types of utility grid as below)

TN-S

TN-C

TN-C-S

TT

L1

L2

L3

N

PE

 

PE

Transformer

Inverter

Transformer

L1

L2

L3

PEN

PE

 

Inverter

L1

L2

L3

N

PE

Transformer

PE

 

Inverter

L1

L2

L3

N

Transformer

PE

 

Inverter

2 Safety Measures & Warning

This manual contains important instructions for GEP series inverter that shall be followed during 
installation of the inverter.
The GEP series for Three or Six MPPT, Three-Phase solar inverter without transformer, which 
consists of  GEP12-L-10, GEP15-L-10, GEP20-L-10, GEP25-10, GEP30-10, GEP36-10, 
GEP29.9-10, GEP30-L-10,GEP35-L-10,GEP50-10 and GEP60-10 model type. 
Model GEP50-10 and GEP60-10 are commercial and industrial PV inverters, cannot be used as 
residential inverters.
The GEP Series have been designed and tested strictly according to the international safety 
regulation. As electrical and electronic equipment, safety instructions related to them must be 
complied with during installation, commissioning, operation. Incorrect or improper work may result 
in damage to:
1. The life and well-being of the operator or a third party.
2. The inverter and other properties that belong to the operator or a third party. Therefore the 
following safety instructions must be read and always kept in mind prior to any work. All detailed 
work-related safety warnings and notes will be specified at the critical points in corresponding 
chapter.
All installation and electrical work must only be performed by qualified personnel. They have:
•Been trained specially.
• Already completely read through and understood the manual and related documents.
• Be familiar with safety requirements for electrical systems.
The inverter must be installed and maintained by professionals in compliance with local electrical 
standards regulations and the requirements of local power authorities or companies.
• Improper handling of this device will pose a risk of injury.
• Always follow the instructions contained in the manual when moving or positioning the inverter.
• The weight of the equipment can cause injuries, serious wounds or bruise if improperly handled.
• Please install it in a place beyond children's reach.  
• Prior to installing and maintaining the inverter, it is crucial to make certain that the inverter in not 
electrically connected.
• Before maintaining the inverter, disconnect the connection between the AC grid and the inverter 
first, and then disconnect the connection between the DC input and the inverter, you should wait 
at least 5mins after these disconnection in case of electric shock.
• All cables must be firmly attached, undamaged, properly insulated, and adequately dimen-
sioned.
• The temperature of some parts of the inverter may exceed 60

 during operation. To avoid 

being burnt, do not touch the inverter during operation. Let it cool before touching it. 
• Without permission, opening the front cover of the inverter is not allowed. Users should not 
touch/replace any components of the inverter except the DC/AC connectors. Manufacturer will not 

bear any consequences caused by unauthorized actions which will lead to potential injury to 
people and damage to inverters.
• Static electricity may damage electronic components. Appropriate method must be adopted to 
prevent such damage to the inverter; otherwise the inverter may be damaged and the warranty 
will be annulled.
• Ensure that the output voltage of the proposed PV array is lower than the maximum rated input 
voltage of the inverter; otherwise the inverter may be damaged and the warranty will be annulled.
• If the equipment is used in a manner not specified by the manufacturer, the protection provided 
by the equipment may be impaired.
• When exposed to sunlight, the PV array will generate very high voltage which can cause 
electrical shock hazard. Please strictly follow the instruction we provided.
• PV modules should have an IEC61730 class A rating.
• Prohibit inserting or pulling the AC or DC terminals when the inverter is operational. Or the 
inverter will be destroyed.
Only DC connectors provided by Manufacturer are permitted for use, otherwise the inverter may 
be damaged and the warranty will be annulled.
• The inverter can exclude the possibility of DC residual currents to 6mA in the system,Where an 
external RCD is required in addition to the built-in RCMU, type A RCD must be used to avoid 
tripping.
• The default photovoltaic module is not grounded.
• It is recommended to add a fuse when there is more than two PV string inputs into one MPPT.
The IP65 premise is that the machine is completely sealed.  Please install it within one day after 
unpacking, otherwise please block the unconnected port and do not open it to ensure that the 
machine is not exposed to water and dust. 
 

Summary of Contents for GEP12-L-10

Page 1: ...UAL Global Sales Service Network GE is a registered trademark of General Electric Company and is used under license by GoodWe Technologies Co Ltd No 90 Zijin Rd New District Suzhou 215011 China www ge...

Page 2: ...7 5 System Operation 21 5 1 LCD Panel And LED 21 5 2 User Interface Introduction 22 5 3 System Configuration 25 5 4 Precaution For Initial Startup 30 5 5 Setting Inverter Parameters via App 31 5 6 Mon...

Page 3: ...work All detailed work related safety warnings and notes will be specified at the critical points in corresponding chapter All installation and electrical work must only be performed by qualified per...

Page 4: ...ons which will lead to potential injury to people and damage to inverters Static electricity may damage electronic components Appropriate method must be adopted to prevent such damage to the inverter...

Page 5: ...ter provides standard interface RS485 WIFI for communication Inverters also provide running recode data display parameter configuration via LCD panel For the main block diagram please refer to chapter...

Page 6: ...ommunication Terminal Grounding Screw Expansion Bolt Safe Screw Connecting Terminal Grounding AC Cover OT Terminal Insulation Sleeve WiFi Module WiFi communication Or without LCD Quick Installation In...

Page 7: ...values The Upward part The downward part The front part Both sides Interval 200mm 500mm 500mm 600mm 1200mm 500mm 1200mm 600mm 600mm 500mm 300mm The Upward part The downward part The front part Both si...

Page 8: ...low these steps to connect the utility and inverter 7 If the diameter of the cable does not match the terminal or if the cable is aluminum cable please contact after sales service Two mounting holes i...

Page 9: ...et of a suitable length with a wire stripper Output Current 31 5A 40A 54 5A 40A 43 3A 48A 53 3A 80A 96A 80A 96A Inverter Model GEP12 L 10 GEP15 L 10 GEP20 L 10 GEP25 10 GEP29 9 10 GEP30 10 GEP36 10 GE...

Page 10: ...not met The GEP series has three PV input area PV1 input PV2 input PV3 input each with MPPT tracker therefore the three PV input can be different with each other including different type of modules di...

Page 11: ...zlogger Pro manual Remote shutdown is only for European installations in compliance with European safety requirements A remote shutdown device is not provided by manufacturer DRED should be connected...

Page 12: ...ion This function is only applicable for WiFi model for specific configurations please refer to WiFi LAN Configuration Instruction in the attachment and you can also refer to the description of Demo V...

Page 13: ...ive On Fault occurred OFF No fault Status Indicator Green green green red light respectively corresponds to 5 2 User Interface Introduction Communication information icon GPRS and WiFi show the signal...

Page 14: ...Fi 22 93 3kWH 4 E TOTAL E DAY 01 01 2020 00 00 00 CARBON Fault Utility Loss 0 0kWH Basic Advanced WiFi 22 105 3kWH 4 E TOTAL E DAY 01 01 2020 00 00 00 Fault WiFi Con guration 22 Basic Advanced 01 01 2...

Page 15: ...0 00 Fault Country Code Holland Northlreland ChinaHigher France 50Hz France 60Hz WiFi 22 01 01 2020 00 00 00 Fault Language WiFi 22 01 01 2020 00 00 00 Fault Data Time WiFi 22 01 01 2020 00 00 00 Faul...

Page 16: ...i 22 01 01 2020 00 00 00 Normal Adv Settings HVRT Grid Type Password Factory Data Reset WiFi 22 01 01 2020 00 00 00 Normal Adv Settings HVRT Grid Type Password Factory Data Reset WiFi 22 01 01 2020 00...

Page 17: ...0 6 0 4 0 2 0 4 6 8 10 12 14 16 18 20 Month Year Basic Advanced 01 01 2020 00 00 00 Fault WiFi Con guration 22 Basic Advanced 01 01 2020 00 00 00 Normal WiFi Con guration 22 01 01 2020 00 00 00 Norma...

Page 18: ...local service office 1 Disconnect the DC switch take off DC connector check PV string voltage check if it exceeds the input voltage in inverter specification 2 If it does please reconfigurate PV panel...

Page 19: ...ber of MPP Trackers Number of Strings per MPPT Output AC Nominal Output Power W Nominal Output Apparent Power VA Max AC Active Power W Max AC Apparent Power VA Nominal Power at 40 W Max Power at 40 In...

Page 20: ...rent A Max Output Fault Current Peak and Duration A ms Inrush Current Peak and Duration A us Nominal Output Current A Power Factor Max Total Harmonic Distortion Efficiency Max Efficiency Europen Effic...

Page 21: ...T Output AC Nominal Output Power W Nominal Output Apparent Power VA Max AC Active Power W Max AC Apparent Power VA Nominal Power at 40 W Max Power at 40 Including AC Overload W Nominal Output Voltage...

Page 22: ...pment in an industrial installation Category IV applies to equipment permanently connected at the origin of an installation upstream of the main distribution board For example electricity meters prima...

Page 23: ...PV plant Caution Before maintenance please disconnect the AC breaker rst and then disconnect DC breaker Wait 5 minutes until the residual voltage has been released 8 1 Clearing The Fan Series inverte...

Reviews: