01
01 Safety Precaution
General Disclaimer
Safety Disclaimer
• The information in this quick installation guide is subject to change due to product updates or other
reasons. This guide cannot replace the product labels or the safety precautions in the user manual
unless otherwise specified. All descriptions here are for guidance only.
• Before installations, read through the quick installation guide and the user manual to learn about
the product and the precautions.
• All installations should be performed by trained and knowledgeable technicians who are familiar
with local standards and safety regulations.
• Check the deliverables for correct model, complete contents, and intact appearance. Contact after
sales service if any damage is found or any component is missing.
• Use insulating tools and wear personal protective equipment when operating the equipment to
ensure personal safety. Wear anti-static gloves, cloths, and wrist strip when touching electron
devices to protect the inverter from damage.
•
Strictly follow the installation, operation, and configuration instructions in this guide and user
manual. The manufacturer shall not be liable for equipment damage or personal injury if you do not
follow the instructions. For more warranty details, please visit https://www.gesolarinverter.com.
DC Side:
1. Ensure the component frames and the bracket system are securely grounded.
2. Connect the DC cables using the delivered DC connectors and terminals. The manufacturer
shall not be liable for the equipment damage if other connectors or terminals are used.
3. Ensure the DC cables are connected tightly and securely.
4. Measure the DC cable using the multimeter to avoid reverse polarity connection. Also, the
voltage should be under the permissible range.
AC Side
1. The voltage and frequency at the connecting point should meet the on-grid requirements.
2. An additional protective device like the circuit breaker or fuse is recommended on the AC side.
Specification of the protective device should be at least 1.25 times the AC output rated current.
3.
PE cable of the inverter must be connected firmly. The resistance between the neutral wire
and the earth cable is less than 10Ω.
4. You are recommended to use copper cables as AC output cables. Contact the manufacturer if
you want to use aluminum cables.
Inverter:
1. Terminals at the bottom of the inverter cannot bear much load. Otherwise, the
terminals will be damaged.
2. All labels and warning marks must be clear after the installation. Do not scrawl,
damage or block any label on the device.
3. Warning labels on the inverter are as following.
Warning