4.3.2 AC circuit breaker and leakage current protection device 

Please install an independent two pole circuit breaker to protect the inverter and make sure it is 

safe to disconnect it from the grid. 
In addition to the built-in RCMU, an external RCD is required to ensure that the inverter system 

does not carry DC residual currents. To avoid tripping, the types A can be used.

Note: it is not recommended that multiple inverters share a single circuit breaker. 
The integrated leakage current detection device of the inverter can detect external leakage current 
in real time. When the detected leakage current exceeds the limit value, the inverter will quickly 
disconnect from the grid. If the leakage current protection device is installed externally, the action 
current should be 300mA or higher.

4.3.3 DC Side Connection

1. Before connecting the PV strings, please ensure the plug connectors have the correct polarity. 
Incorrect polarity has the potential risk to cause permanent damage to the inverter.  
2. The open circuit voltage of the PV strings cannot exceed the maximum input voltage of the 
inverter.

3. Only the DC connectors supplied by the manufacturer are suitable for use. 
4. The positive and negative pole should not be connected to the PE wire (ground wire). Not 
following this instruction may cause damage to the inverter. 

5. Red wire represents positive, black wire represents negative.
6. For the GE series the minimum insulation resistance to the ground of the PV panels must 

exceed 20kΩ(R=600/30mA). There is risk of electric shock if this minimum resistance requirement 

is not met. 

Inverter Model

GEP4.6-1C-10/GEP5.0-1C-10

GEP7.0-1-10/GEP8.5-1-10

GEP9.0-1-10/GEP10-1-10

Recommended Circuit Breaker Specifications

32A

50A

63A

Please use solar PV cable in DC 
connection.(4mm PV1-F wire recommended)

There are four types of DC connectors, DEVALAN, MC4, AMPHENDL H4  and QC4.10 series. 

DEVALAN SERIES

MC4 SERIES

AMPHENOL SERIES

QC4.10 SERIES

Note: The actual DC connector used is shown in the accessory box.

DC cable specification:

Value

4~5mm

2.5~4mm

2

About 7mm

Label

A

B

C

Description

External diameter of wire stock

Cross-sectional area of conductor material

Length of bare wire

A

B

C

Please use special tools to do crimping

MC4 & QC4.10

DEVALAN & AMPHENOL

Do not crimp wire 

into the limit buckle.

Negative connector

Positive connector

Inverter side

The installation method of DC connector.

Step 3:

 Connect the assembled AC cables into AC terminals with fastening torque about 

2.0-2.5N.m. Then lock the cover and screw the cap.

Screwing torque 2.0-2.5N.m

Note:There is risk of burning if the DC connector is not connect tightly,you can hear the 
“Click” sound to confirm the connectivity.

09

10

Summary of Contents for GEP5.0C

Page 1: ...3 support au gesolarinverter com sales au gesolarinverter com Global Sales Service Network GEP 4 6 10KW SINGLE PHASE USER MANUAL GE is a registered trademark of General Electric Company and is used un...

Page 2: ...l Connection 08 4 4 Communication Connection 12 5 System Operation 16 5 1 LCD Panel 16 5 2 User Interface and System Configuration 17 5 3 Wi Fi LAN Reset Wi Fi LAN Reload 22 5 4 Precaution for Initial...

Page 3: ...d to prevent such damage otherwise the warranty may be null and void Ensure the output voltage of the proposed PV array is lower than the maximum rated input voltage of the inverter otherwise the inve...

Page 4: ...y extension solution for our customer For further details please visit www gesolarinverter com Item 1 2 3 4 5 6 7 8 9 Name DC Switch PV Input Terminal Wi Fi LAN Module Optional DRED Function Optional...

Page 5: ...be installed near flammable and explosive items Strong electro magnetic charges should be kept away from installation site 4 Product label and warning symbols should be located and placed in a manner...

Page 6: ...Grade A B C D Description Outside diameter Separated wire length Conductor wire length Conductor core section Value 13 18mm 20 25mm 7 9mm 2 5 10mm2 D A B Annealed copper wire C Cables Screw cap AC sh...

Page 7: ...PE wire ground wire Not following this instruction may cause damage to the inverter 5 Red wire represents positive black wire represents negative 6 For the GE series the minimum insulation resistance...

Page 8: ...d metal parts of the equipment and other enclosures in the PV power system must be grounded Please follow the steps below to connect PE cable to ground L1 L2 L1 1 2mm Step 1 Strip the wire insulation...

Page 9: ...installations in compliance with Australian and New Zealand safety requirements and DRED is not provided by the manufacturer DRED should be connected to the COM port with 6 Pin as illustrated below P...

Page 10: ...ion of commu nication connection you can access portal gesolarinverter com or download the Power Sight App by scanning the QR code to monitor your PV plant and device Please contact after sales for fu...

Page 11: ...6000W Or Or Power Limit ON Pac 6000W Power Limit OFF Pac 6000W Set Power Limit XXX Set Power Limit XXX Set Modbus Addr Pac 6000W Short Press Long Press Short press short press to select Leading or Lag...

Page 12: ...E Today menu which displays the total power generation for today Short press the button to enter the E Total menu which displays the total power generation up to today Short press the button to enter...

Page 13: ...et Power Limit XXX Long press 2S 6 Operation of display under grid connected mode When the input voltage reaches the inverter s start up voltage the LCD starts to work the yellow light will be turned...

Page 14: ...ecifically according to the inverter Modbus address and Modbus register value according to the set range to set the corresponding value PF Power Curve Mode Function PF curve mode enable or disable B P...

Page 15: ...e refer to the following instructions before contacting your local service If any problems arise the red FAULT LED indicator on the front panel will light up and the LCD screen will display relevant i...

Page 16: ...s possible that there are special characters not supported by the module in the hotspot password Please modify the password so that it consists of only Arabic numerals or uppercase lowercase letters...

Page 17: ...20 360 80 600 0 13 13 13 16 3 16 3 16 3 3 1 1 1 4600 4600 230V 50 20 3 150 120 80 97 7 97 3 GEP7 0S 13500 600 80 550 80 120 360 80 600 0 13 13 13 16 3 16 3 16 3 3 1 1 1 7000 7000 230V 3 50 1 35 1 Adju...

Page 18: ...es Moisture Location Category Definition Environment Category Definition Outdoor the ambient air temperature is 20 50 Relative humidity range is from 4 to 100 applied to PD3 Indoor unconditioned the a...

Reviews: