48
Design and specifications are subject to change without notice
S47183-e 01/2008
7. Customer support.
7.1 PST coding system.
•
The PST coding system is a new way
•
to configure Gerapid according to customer needs. It
has been released in 2008 and it’s not related with
any previous ordering forms.
•
This code consists of 20 digits. Every digit means cer-
tain rated value or component that might be installed
in the breaker.
•
Table 7
shows all available values, components and
accessories for the Gerapid breaker family. Most of
them are describe in section 3 of this manual. Please
contact GE Sales representative in case of any ques-
tions.
•
This system is valid for Gerapid line feeder type (F),
rectifier type (R) and disconnector type (DS). However
this instruction relates only to standard, line feeder
type.
•
Not all of the configurations are possible to order. Us-
ing the electronic version of the Ordering Form, avoid
a wrong configuration selection.
•
This Excel ® based tool enable in fast and mistake
proof manner to generate PST code and Ordering
Form. Ask your GE Representative details. The number
of this tool is:
APN460437
.
Table 7.
1
2
3
4
5
6
7
8
9
10 11 12 13 14 15 16 17 18 19
20
Breaker Type (Code 1)
Delivery Version (Code 20)
1 2607
5 8007R
China
3
Standard
1
2 4207
6 10007R
On Request
R
US
2
3 6007
7 8007DS
4 8007
Control Terminal Type (Code 19)
Arc Chute (Code 2)
32pole Harting
3 Standard
1
1 1X2 (1000V)
4 2X2 (2000V)
S 2X2S (2000V)
108 pole Harting
4 DAD Connector 2
2 1X3 (1500V)
5 2X3 (3000V)
E
On Request
R
3 1X4 (2000V)
6 2X4 (3600V)
Counter (code 18)
Drive Supply Voltage (Code 3)
Without
0
1 48 V DC
5 220 V DC
9 125 V AC
With Mechanical Counter
1
2 60 V DC
6 250 V DC
A 230 V AC
With Electronic Counter & Battery
2
3 110 V DC
7 110 V AC
B 240 V AC
4 125 V DC
8 120 V AC
R On Request
Arc Chute Indicator (Code17)
With
1
Without
0
Connectors (Code 4)
1 H/H
4 V/V
B
BBRail
Hand Lever (Code 16)
2 H/V
5 SEL 6kA
S
Siemens
With
1
Without
0
3 V/H
6 SEL 12kA
R
On Request
Sidewall Protection (Code 15)
Polarization (Code 5)
With
1
Without
0
1 '+'
2 '-'
0 Not important
AP Cover
2
SEL Type (Code 6)
Position Indicator (Code 14)
1 35C
0 No SEL
With
1
Without
0
2 55C
Force Tripping Unit (Code 13)
Overcurrent Trip (Code 7)
With
1
Without
0
1 Fixed 1-12 kA
5 Polarized adjust. 0,4-1,2 kA
0 W/O Trip
2 Adjust.1-12 kA
6 Polarized adjust. 0,8-2,5 kA
ED Coil (Code12)
3 Fixed 12-24 kA
7 Polarized adjust. 2,0-6,0 kA
With ED-Coil and internal C-bank (NEKO)
2
Without
0
4 Adjust.12-24kA
8 Polarized adjust. 4,0-8,0 kA
With ED-Coil and 3C-bank (BBRail only)
3
With ED-Coil and external C-Bank
1
Voltage Converter (Code 8)
Auxiliary Tripping Unit(Code 11)
1 24V DC±5% ext.
4 88..143V DC
Shunt Trip 125V DC
4
Without
0
2 24/24 VDC
5 125..353 V DC 115..240V AC
Shunt Trip 220V DC
5
ST with external 24VDC supply
1
3 35..85V DC
R On Request
Undervoltage Release 24 V DC
6
Shunt Trip 24V DC (standard)
2
On Request
R
Shunt Trip 110 V DC
3
Auxilliary Switch (Code 9)
OC Indicator (Code 10)
1 3 Aux. Contacts
3 9 Aux. Contacts
R
Other quantity
With
1 Without
0
2 5 Aux. Contacts
4 10 Aux. Contacts
PST code positions
EF4/12