Chapter 2. Installation
GFK-2892F
March 2019
23
Fault Notifications
Powering up or down, or connecting/disconnecting the GCG001 from the controlling PROFINET device will have
effects specific to the particular controlling device. The discussion below relates to using the RX3i PROFINET
Controller as the controlling device.
Removing a GCG001 from the PROFINET network causes a
Loss of Device
fault for the GCG001 itself and all
Genius devices connected via that GCG001.
Adding a GCG001 to the PROFINET network causes an
Addition of Device
fault for the GCG001 itself and all
Genius devices connected via that GCG001.
Note that when a GCG001 is replaced by a successor GCG001, it is important to ensure that the successor is
configured for PROFINET in the same manner as its predecessor. The quickest way to ensure this is to remove
the SD Card from the original and insert it into the successor GCG001.