Chapter 3. Configuration
30
PACSystems RX3i Genius Communications Gateway
GFK-2892F
Figure 18: Populating the Genius IO Devices to be Controlled by the Genius Gateway
13.
Special consideration needs to be given to the configuration of a Series 90-70 Remote I/O Scanner
(BEM733) device on the Genius Bus, since this device is capable of controlling a rack filled with I/O
modules, each of which needs to be suitably configured.
a.
Add the BEM733 to the Genius Bus configuration as described above.
b.
Drill down into the BEM733. A display of rack I/O will be presented (Figure 19).
Figure 19: Populating Slots in S90-70 Rack Controlled by Remote I/O Scanner (BEM733)