Chapter 6. COMMREQ/Data_Init_Comm Programming
74
PACSystems RX3i Genius Communications Gateway
GFK-2892F
Read Identification Reply Data
The datagram returned by the target Genius Device has the following data content:
Word #
Description
MSB
LSB
0
Output data length (bytes)
Input data length (bytes)
1
Number of diagnostic data bytes
Number of configuration data bytes
2
Device Status Table Address (LSB)
Device Status Bits
Bit
Description
0
Device Forced if set to 1
1,2 01 = inputs only
10 = outputs only
11 = combination
3
HHM Present if set to 1
4
BSM Present if set to 1
5
BSM Controller if set to 1
6
BSM Actual State
7
BSM Forced if set to 1
3
Device Model Number OR
GENA application ID if a GENA
Device Status Table Address (MSB)
4
Assigned controller bus address
OR S6 GBC DIP switch, if S6 GBC
OR GENA application rev #, if GENA
Device Software Revision Number
5
Baud Rate Code
Bits
Baud Rate
0 0 0 0 x x x x 153.6 K baud, extended
0 0 0 1 x x x x 153.6 K baud, standard
0 0 1 0 x x x x 76.8 K baud
0 0 1 1 x x x x 38.4 K baud
Device Model Number