FlexLink-Gas Connection
The FlexLink gas connections consist of metal corrugated tubes
that are elastic to ensure that the connection of the gas couplings to
the pole columns is particularly easily possible.
The gas connections are firmly connected to the density monitor
unit on one side. The other side has a filling coupling with check
valve for connection to the pole columns.
FlexLink is available for the standard density monitor unit as well as
for the EasyCheck technology.
12.2.1
Setup of the FlexLink-Gas Connction
The FlexLink technology makes it particularly easy to couple the
gas connections to the pole columns.
B
1
A
B
2
3
B
D
Left-hand thread
flex_link_gas
verrohr
ung
A
1
FlexLink gas piping pole A
1x
2
FlexLink gas piping pole B
1x
3
FlexLink gas piping pole C
1x
4
Density monitor
1x
B
Gas pipe / filler coupling
30 Nm
D
Central fill connection / filler block
30 Nm
E
Threaded sleeve / filler block
30 Nm
Left-hand
thread
Summary of Contents for GL 311 F3/4031 P/VE
Page 2: ......
Page 10: ...INTRODUCTION 10 146 OI 250 EN REV7 REV6...
Page 12: ...SAFETY 12 146 OI 250 EN REV7 REV3...
Page 48: ...INSTALLATION 48 146 OI 250 EN REV7 REV7...
Page 80: ...INSPECTION AND MAINTENANCE 80 146 OI 250 EN REV7 REV3...
Page 102: ...RECONDITIONING 102 146 OI 250 EN REV7 REV7...
Page 104: ...END OF LIFE MANAGEMENT 104 146 OI 250 EN REV7 REV2a...
Page 114: ...SPECIAL EQUIPMENT OPTIONAL 114 146 OI 250 EN REV7 REV0...
Page 128: ...REPLACEMENT PARTS AND ACCESSORIES 128 146 OI 250 EN REV7 REV6...
Page 130: ...HANDLING USED SULFUR HEXAFLUORIDE 130 146 OI 250 EN REV7 REV2...