I
NSTALLATION
REV7
/REV7
OI 250 (EN)
6.7
Mounting the Density Monitor and Filler Block to Pole B
• Mount the density monitor, filler block and bracket (1) using the
bolt (2), washer (3) and nut (4) at the specified position on the
lattice support (view X). Tighten to a torque of 25 Nm.
In breaker configurations with three density monitors, the list
below must be repeated for poles A and C. The design of the
mounting bracket for the density monitor may differ from the
picture shown below.
1
Density monitor, filler block and bracket
1x
2
Bolt, M8 x 20 A2-70
2x
3
Washer, 8.4 A2
2x
4
Nut, M8 A2-70
2x
1
BA-
P-V
E
-1
2040021_4
BA
-P-V
E-2