• To lift the operating mechanism, use two slings and the locating
pins on the side surfaces of the mechanism.
• Loop one end of each sling under two locating pins and hook the
other end in the crane hook.
• Lift the operating mechanism (1) and position it in front of the
lattice support.
• Lubricate four bolts (14) as described in L1 and insert them along
with washers (12) and (15) into the mechanism from the lattice
support side. Make sure that washer (15) is seated between the
support and the mechanism.
• Screw nuts (13) and washers (12) loosely on the four bolts inside
the mechanism.
• Push the mechanism as far to the left as possible in the direction
of pole B and tighten the four nuts.
Tighten to a torque of 196 Nm.
• Replace the spring guard plate (8) and fasten it to the mechanism
using two screws (7). Tighten to a torque of 23 Nm.
1
Operating mechanism
1x
10
Lattice support
1x
12
Washer, 16 A2
8x
13
Hexagon nut, M16 A2-70
4x
14
Hexagon bolt, M16x90 8.8 TZN
4x
15
Washer 16 TZNO / t=8mm
4x
2040021_3
Summary of Contents for GL 311 F3/4031 P/VE
Page 2: ......
Page 10: ...INTRODUCTION 10 146 OI 250 EN REV7 REV6...
Page 12: ...SAFETY 12 146 OI 250 EN REV7 REV3...
Page 48: ...INSTALLATION 48 146 OI 250 EN REV7 REV7...
Page 80: ...INSPECTION AND MAINTENANCE 80 146 OI 250 EN REV7 REV3...
Page 102: ...RECONDITIONING 102 146 OI 250 EN REV7 REV7...
Page 104: ...END OF LIFE MANAGEMENT 104 146 OI 250 EN REV7 REV2a...
Page 114: ...SPECIAL EQUIPMENT OPTIONAL 114 146 OI 250 EN REV7 REV0...
Page 128: ...REPLACEMENT PARTS AND ACCESSORIES 128 146 OI 250 EN REV7 REV6...
Page 130: ...HANDLING USED SULFUR HEXAFLUORIDE 130 146 OI 250 EN REV7 REV2...