I
NSTALLATION
OI 250 (EN)
REV7
/REV7
6.11
Connecting the Cables
To avoid working on gas-filled pole columns, we recommend that
the cables (1) be connected to the circuit breaker's high voltage ter-
minal pads (2) before the pole columns are filled with gas.
The ends of the cables facing away from the circuit breaker (1a)
must not be connected yet.
Cable ends (1a) must not be in contact with earth potential (potenti-
al to ground) simultaneously during later commissioning tests. The
resulting auxiliary circuit would affect the test results.
• Brush the contact surfaces of high voltage terminal pads (2) and
cable clamp (1) until all oxide film has been removed.
• Lubricate contact surfaces on both sides in accordance with
lubrication specification L3.
• Bolt high voltage terminal pads and cable clamp together.
• Keep cable end (1a) isolated from earth potential (potential to
ground).
Improper connection of cables can pose a threat to personnel
and system safety.
The individual responsible for safety must give approval for con-
necting the cables.
When connecting the cables after filling the circuit breaker to
rated pressure, there is the danger that insulators will burst if
they have been damaged.
Therefore:
- The cables may only be connected by qualified personnel
using extreme caution.
DANGER
DANGER
1
Cable with cable clamp
1x
1a
Cable, end facing away from breaker
-
2
High voltage terminal pads
1x
1a
1
2
B
A
-P
-HS
-A
N
S
CHLUS
S
-1
Summary of Contents for GL 311 F3/4031 P/VE
Page 2: ......
Page 10: ...INTRODUCTION 10 146 OI 250 EN REV7 REV6...
Page 12: ...SAFETY 12 146 OI 250 EN REV7 REV3...
Page 48: ...INSTALLATION 48 146 OI 250 EN REV7 REV7...
Page 80: ...INSPECTION AND MAINTENANCE 80 146 OI 250 EN REV7 REV3...
Page 102: ...RECONDITIONING 102 146 OI 250 EN REV7 REV7...
Page 104: ...END OF LIFE MANAGEMENT 104 146 OI 250 EN REV7 REV2a...
Page 114: ...SPECIAL EQUIPMENT OPTIONAL 114 146 OI 250 EN REV7 REV0...
Page 128: ...REPLACEMENT PARTS AND ACCESSORIES 128 146 OI 250 EN REV7 REV6...
Page 130: ...HANDLING USED SULFUR HEXAFLUORIDE 130 146 OI 250 EN REV7 REV2...